CHAPTER 4 - BOILER PIPING
4.5. Additional Limit Control
If a separate Low Water Cut Off (LWCO) is required by
the local jurisdiction or when the boiler is installed
above the system piping, the following guidelines
must be followed:
• The LWCO must be designed for water installations,
electrode probe-type is recommended.
• The LWCO must be installed in a tee connection on
the boiler supply piping above the boiler.
• Wiring of the LWCO to the PRESTIGE Solo is done
directly onto the low voltage terminal strip. Ref-
erence
Fig. 21 on page 34
for available external
limit (manual or auto reset) terminals.
If the installation is to comply with ASME or Canadian
requirements, an additional high temperature limit
may be required. Consult local code requirements to
determine compliance. The limit should be installed as
follows:
• Install the limit in the boiler supply piping between
the boiler and any isolation valve.
• Consult heat exchanger for maximum temperature
set point.
• For wiring of the limit, reference
Fig. 21 on page
34.
Wire the limit to the manual reset terminals
on the low voltage terminal strip. An open manual
reset limit will require a manual reset of the control.
4.6. Backflow Preventer
• Use a backflow preventer valve in the make-up wa-
ter supply to the unit as required by local codes.
4.7. Boiler System Piping Applications
• It is recommended on all piping applica-
tions to utilize a primary/secondary piping
arrangement as a means to provide freeze
protection of the boiler, which is an integral
function of the boiler control. Maintain at
least the minimum boiler flow rate shown
in the Graphs of Chapter 19 on page 89.
For other piping arrangements, contact
Triangle Tube Technical Support or con-
sult other approved/recognized design ar-
rangements.
• On piping applications utilizing a single zone
or other recognized piping design arrange-
ments, it is recommended that the installer
uses flow/check valves with weighted seats at
or near the PRESTIGE Solo to prevent gravity
circulation.
BEST PRACTICE
Boiler
Supply
Boiler
Return
System
Supply
Cold
Water
Fill
System
Return
12"
Max.
Fig. 7 - Near Boiler Piping - Diaphragm Expansion Tank
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......