6
CHAPTER
2
CHAPTER 2 - COMBUSTION AIR & VENTING
• Two Permanent Opening Method
. Two permanent
openings, one commencing within 12 in. of the top
and one commencing within 12 in. of the bottom
of the enclosure, shall be provided. The openings
shall communicate directly, or by ducts, with the
outdoors or spaces that freely communicate with
the outdoors, as follows:
• Where directly communicating with the out-
doors or where communication to the outdoors
is through vertical ducts, each opening shall
have a minimum free area of 1 sq. in./4000 Btu/
hr of total input rating of all equipment in the
enclosure.
See Fig. 3 below.
• Where communicating with the outdoors is
through horizontal ducts, each opening shall have
a minimum free area of not less than 1 sq.in./2000
Btu/hr of total input rating of all equipment in the
enclosure.
See Fig. 4 below.
2.4.3 Combination of Indoor and Outdoor
Combustion Air
Indoor Openings.
Where used, openings connecting the in-
terior spaces shall comply with
Section 2.4.1 on page 5
.
Outdoor Opening(s) Location
. Outdoor opening(s) shall
be located in accordance with
Section 2.4.2 on page 5
.
Outdoor Opening(s) Size
. Outdoor opening(s) shall be
calculated in accordance with the following:
• The ratio of the interior spaces shall be the avail-
able volume of all communicating spaces divided
by the required volume.
• The outdoor size reduction factor shall be 1 minus
the ratio of interior spaces.
• The minimum size of outdoor opening(s) calculat-
ed in accordance with the above outdoor air chap-
ter multiplied by the reduction factor. The mini-
mum dimension of air openings shall not be less
than 3 in.
2.5. Combustion Air and Vent Piping
The PRESTIGE Solo requires a Category IV venting sys-
tem, which is designed for pressurized venting and
condensate.
The PRESTIGE Solo is certified as a Category IV or Direct
Vent (sealed combustion) appliance. A Category IV ap-
pliance utilizes uncontaminated indoor or outdoor air
surrounding the appliance for combustion. A Direct Vent
appliance utilizes uncontaminated outdoor air piped di-
rectly to the appliance for combustion.
Do not install the PRESTIGE Solo into a com-
mon vent with any other gas or oil appliances.
This will cause flue gas spillage or appliance
malfunction, which will result in substantial
property damage, serious injury, or death.
DANGER
Fig. 3 - All Combustion Air from Outdoors Through
Ventilated Attic
Fig. 4 - All Combustion Air from Outdoors Through
Horizontal Ducts
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......