46
CHAPTER
9
CHAPTER 9 - ACVMAX OPERATION
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
CH1 Setpoint
140°F
68°F
188°F
CH2 Setpoint
140°F
68°F
188°F
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Select CH Demand
prompts the installer to select how a CH De-
mand is generated
.
Thermostat & Setpoint
- A central heating call from a thermostat
or zone panel will enable the Prestige and the setpoint will be fixed
for central heating calls. After Thermostat & Setpoint is selected, the
CH1 Setpoint
screen appears. (see below).
Constant & Setpoint
- The Prestige will maintain setpoint without
an external CH call from a thermostat or zone panel. The setpoint
will be fixed for CH calls. After Constant & Setpoint is selected, the
CH1 Setpoint screen appears.
CH1 Setpoint
prompts to enter the fixed setpoint for a CH1 heating
call when a Setpoint option is chosen in Select CH Demand.
Press the
LEFT
or
RIGHT
buttons to adjust the temperature setpoint
then press
OK
to store the setting. The
CH2 Setpoint
screen then
appears.
CH2 Setpoint
prompts to enter the fixed setpoint for a CH2 heating
call when a Setpoint option is chosen in Select CH Demand.
Press the
LEFT
or
RIGHT
buttons to adjust the temperature setpoint
then press
OK
to store the setting and complete the Heating EZ Set-
up.
CH1 Default: 140°F [60°C]
CH2 Default: 140°F [60°C]
9.7. Heating EZ Setup
Heating EZ Setup allows the installer to quickly customize the central heating settings for the application.
9.7.1 Select CH Demand (No outdoor sensor connected)
0 - 10V Modulation Signal
- This option allows the Prestige firing
rate to be controlled by an external control system.
Refer to
Chapter 13 on page 65
for more information.
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......