89
CHAPTER
1
9
CHAPTER 19 - PRODUCT SPECIFICATIONS
Boiler
Model
Fuel
Input
DOE
Heating Capacity
Net AHRI
Rating
AFUE
Shipping
Weight
Lbs / Kg
Solo 80
Natural
Propane
16,000 -
80,000
74,000
64,000
95%
103 / 47
Solo 110
Natural
Propane
20,000 -
110,000
102,000
89,000
95%
103 / 47
Solo 155
Natural
Propane
27,800 -
153,000
142,000
123,000
95%
118 / 53.5
Solo 175
Natural
Propane
30,900 -
170,000
157,000
137,000
95%
128 / 58
Solo 250
Natural
Propane
43,600 -
240,000
222,000
193,000
95%
140 / 63.5
Solo 299
Natural
Propane
72,500 -
299,000
278,000
242,000
95%
210 / 95
Boiler
Model
Fuel
Input
Output
Net AHRI
Rating
Combustion
Efficiency
Thermal
Efficiency
Shipping
Weight
Lbs / Kg
Solo 399
Natural
Propane
72,500 -
399,000
379,000
330,000
94.1%
95.1%
216 / 98
• The heating capacity of the PRESTIGE Solo 80/110/155/175/250/299 is based
on the test requirements of the U.S. Department of Energy.
• The AHRI rating is based on a piping and pick up allowance of 1.15. This al-
lowance should be sufficient for standard radiation requirements.
• Based on the given AFUE the PRESTIGE Solo 80/110/155/175/250/299 meets
the energy efficiency guidelines established by Energy Star.
• Input and output ratings are shown for sea level applications. The PRESTIGE
Solo automatically derates the input at approximately 2% for every 1,000 Ft.
of altitude. No alterations to the boiler or burner system are required.
• PRESTIGE Solo 399 output rating is based off of the thermal efficiency.
NOTICE
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......