RT-PRC024-EN
59
Performance Data
(15 Tons High Efficiency)
Table 41. Evaporator Fan Performance 15 Tons with Gas Heat Y*D181C Dehumidification (Hot Gas Reheat) Option Downflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & Field Supplied Low Static Drive
(i)
(i)
Field Supplied Fan Sheave BK120 required. Field Supplied Belt may be necessary.
3-HP Standard Motor & Drive
4800
427 0.88
463
1.03
496
1.16
527
1.31
557
1.46
586
1.61
614
1.77
641
1.93
667
2.10
693
2.29
5400
471 1.21
505
1.38
535
1.53
564
1.69
591
1.85
618
2.02
644
2.19
669
2.36
695
2.54
718
2.72
6000
516 1.61
547
1.81
576
1.98
603
2.15
628
2.33
653
2.51
677
2.70
700
2.88
724
3.07
747
3.26
6600
561 2.09
590
2.32
617
2.52
643
2.71
667
2.90
690
3.09
712
3.29
734
3.49
756
3.70
777
3.90
7200
607 2.67
634
2.92
659
3.16
683
3.36
707
3.56
728
3.77
749
3.98
770
4.20
791
4.42
811
4.64
5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & Drive
3-HP Standard Motor & High Static Drive Accessory
4800
719 2.49
742
2.69
765
2.89
787
3.09
808
3.28
829
3.48
849
3.68
869
3.89
887
4.09
906
4.29
5400
742 2.91
765
3.12
788
3.34
810
3.56
831
3.79
852
4.01
872
4.24
891
4.46
909
4.67
928
4.91
6000
769 3.46
791
3.66
812
3.87
833
4.09
855
4.33
874
4.57
894
4.81
913
5.06
932
5.31
950
5.56
6600
799 4.11
819
4.32
840
4.53
860
4.75
879
4.98
899
5.22
918
5.46
937
5.72
—
—
—
—
7200
830 4.86
850
5.09
870
5.31
888
5.54
—
—
—
—
—
—
—
—
—
—
—
—
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference
Table 51
.
For Oversized Evaporator Fan Speed (RPM), reference
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
Summary of Contents for Voyager TC Series
Page 84: ...84 RT PRC024 EN Figure 3 12 5 25 Tons Cooling with Optional Electric Heat Typical Wiring...
Page 106: ......
Page 107: ......