Mechanical Specifications

Controls

Unit shall be completely factory 
wired with necessary controls and 
contactor pressure lugs or terminal 
block for power wiring. Unit shall 
provide an external location for 
mounting a fused disconnect device. 
ReliaTel controls shall be provided 
for all 24 volt control functions. The 
resident control algorithms shall 
make all heating, cooling, and/or 
ventilating decisions in response to 
electronic signals from sensors 
measuring indoor and outdoor 
temperatures. The control algorithm 
maintains accurate temperature 
control, minimizes drift from set 
point, and provides better building 
comfort. A centralized control shall 
provide anti-short cycle timing and 
time delay between compressors to 
provide a higher level of machine 
protection. 

Defrost Controls 

Adaptive demand defrost shall be 
provided to permit defrost wherever 
coil icing conditions begin to 
significantly reduce unit capacity. 

Factory Installed Options

Black Epoxy Coated Pre-Coated 
Coils

The black epoxy coils have a 
thermoset vinyl coating that is 
bonded to the aluminum fin stock 
prior to the fin-stamping process. 
The pre-coated coils are an 
economical option for protection in 
mildly corrosive environments.

Dehumidification Option

The dehumidification (hot gas reheat) 
option shall provide increased 
dehumidification. The option shall 
consist of a hot-gas reheat coil 
located on the leaving air side of the 
evaporator coil prepiped and 
circuited. Low pressure switch(es) 
and thermostatic expansion valve(s) 
TXV are standard. Frostat™, ReliaTel 
options module, and 2" pleated filters 
are required but not standard. They 
must be ordered and configured 
separately.

High Efficiency Motors 

This option is available with 
efficiency ratings from 86.5 up to 
91.0. It is not available for all models.

High Pressure Cutout

This option is offered for units that 
do not have High Pressure cutout as 
standard. 

Hinged Access Doors

Sheet metal hinges are available on 
the Filter, Evaporator, Fan/Motor and 
the Compressor/Control Access 
Doors. This option is available on all 
models.

Powered or Unpowered 
Convenience Outlet 

This option is a GFCI, 120v/15amp, 2 
plug, convenience outlet, either 
powered or unpowered. When the 
convenience outlet is powered, a 
service receptacle disconnect will be 
available. The convenience outlet is 
powered from the line side of the 
disconnect or circuit breaker, and 
therefore will not be affected by the 
position of the disconnect or circuit 
breaker. This option can only be 
ordered when the Through the Base 
Electrical with either the Disconnect 
Switch, or Circuit Breaker, option is 
ordered. This option is available on 
all downflow models (Gas/Electric 
Only).

Stainless Steel Heat Exchanger

Gas heat exchanger shall be of drum 
and tube design constructed from a 
minimum 304 Grade stainless steel. 
The stainless steel heat exchanger 
shall have a 10-year warranty as 
standard (Gas/Electric Only). 

Supply and/or Return Air Smoke 
Detector

 With this option installed, if smoke is 
detected, all unit operation will be 
shut down. Reset will be manual at 
the unit. Return Air Smoke Detectors 
require minimum allowable airflow 
when used with certain models. See 
the Installation, Operation, and 
Maintenance (IOM) manual for the 
models affected and the minimum 
allowable airflow required. 

Through the Base Electrical with 
Circuit Breaker 

This option is a thermal magnetic, 
molded case, HACR Circuit Breaker 
with provisions for through the base 
electrical connections. The circuit 
breaker will be installed in a water 
tight enclosure in the unit with 
access through a swinging door. 
Factory wiring will be provided from 
the switch to the unit high voltage 
terminal block. The circuit breaker 
will provide overcurrent protection, 
be sized per NEC and UL guidelines, 
and be agency recognized by UL/
CSA. This option is available on all 
downflow models.

Through the Base Electrical With 
Disconnect Switch

Three-pole, molded case, disconnect 
switch with provisions for through 
the base electrical connections are 
available. The disconnect switch will 
be installed in the unit in a water tight 
enclosure with access through a 
swinging door. Factory wiring will be 
provided from the switch to the unit 
high voltage terminal block. The 
switch will be UL/CSA agency 
recognized. Note: The disconnect 
switch will be sized per NEC and UL 
guidelines but will not be used in 
place of unit overcurrent protection. 
This option is available on all 
downflow models.

Through the Base Utilities Access

An electrical service entrance shall be 
provided allowing electrical access 
for both control and main power 
connections inside the curb and 
through the base of the unit. Option 
will allow for field installation of 
liquid-tight conduit and an external 
field installed disconnect switch.

Two-Inch Pleated Filters 

Two inch pleated media filters shall 
be available on all models.

Summary of Contents for Voyager TC Series

Page 1: ...Packaged Cooling Gas Electric Rooftops May 2007 RT PRC024 EN Voyager 12 25 Tons 60 Hz Packaged Cooling TC Packaged Gas Electric YC...

Page 2: ...application flexibility Voyager continues to provide the highest standards in quality and reliability comfort ease of service and the performance of Trane light commercial products Trane customers dem...

Page 3: ...plication Considerations 11 Selection Procedure 12 Model Number Description 14 General Data 16 Performance Data 26 Controls 72 Electrical Data 74 Jobsite Connections 83 Typical Wiring 84 Dimensional D...

Page 4: ...nty7 Supply and or Return Air Smoke Detector4 13 Thermal Expansion Valve16 Through the Base Electrical Access Through the Base Electrical with Circuit Breaker14 15 Through the Base Electrical with Dis...

Page 5: ...ters provide improved compressor reliability by warming the oil to prevent migration during off cycles or low ambient conditions These are standard on all Voyager models Efficiencies Standard or High...

Page 6: ...riety of Options Factory Installed Options Black Epoxy Pre Coated Coils The pre coated coils are an economical option for protection in mildly corrosive environments Circuit Breaker Required with Thro...

Page 7: ...d means of relieving excess building pressure Clogged Filter Fan Failure Switch A dedicated differential pressure switch is available to achieve active fan failure indication and or clogged filter ind...

Page 8: ...properly installed in the economizer control circuitry this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position Roof Curbs Available for downf...

Page 9: ...ens electrical spikes by staging on fans compressors and heaters Intelligent Fallback is a benefit to the building occupant If a component goes astray the unit will continue to operate at predetermine...

Page 10: ...10 RT PRC024 EN Features and Benefits Figure 1 Voyager Factory Installed Options Factory Installed Options...

Page 11: ...side of the unit Application of this product should be within the cataloged airflow and cooling considerations Barometric Relief This product line offers an optional barometric relief damper for use i...

Page 12: ...the table gives a formula to calculate Fan Motor Heat 3 15 x bhp MBh 3 15 x 2 56 8 06 MBh Now subtract the fan motor heat from the gross cooling capacity of the unit Net Total Cooling Capacity 184 MB...

Page 13: ...nect MA and SA on psychrometric chart with cooling curve Step 3b Determine leaving unit temperature in standard cooling mode Repeat Step 3a substituting net sensible or latent capacity for gross sensi...

Page 14: ...15 Tons High Efficiency 210 17 Tons Standard Efficiency 211 17 Tons High Efficiency 240 20 Tons Standard Efficiency 241 20 Tons High Efficiency 300 25 Tons Standard Efficiency 301 25 Tons High Effici...

Page 15: ...ectrical and either Unit Mounted Disconnect or Circuit Breaker 7 Available factory installed on downflow AND horizontal units Verify with ordering system 8 The Novar control option includes the follow...

Page 16: ...e 0 375 17 50 2 15 Short Orifice 1 1 00 NPT Hi Performance 0 375 17 50 2 15 Short Orifice 1 1 00 NPT Hi Performance 0 375 17 50 2 15 Short Orifice 1 1 00 NPT Outdoor Fan Type Number Used Diameter in D...

Page 17: ...ons and in accordance with ARI Standard 210 240 or 360 iii Integrated Part Load Value is rated in accordance with ARI Standard 210 240 or 360 Units are rated at 80 F ambient 80 F entering dry bulb and...

Page 18: ...NPT Hi Performance 0 375 26 00 2 15 Short Orifice 1 1 00 NPT Hi Performance 0 375 26 00 2 15 Short Orifice 1 1 00 NPT Outdoor Fan Type Number Used Diameter in Drive Type No Speeds CFM Number Motors HP...

Page 19: ...60 93 ii EER is rated at ARI conditions and in accordance with ARI Standard 210 240 or 360 iii Integrated Part Load Value is rated in accordance with ARI Standard 210 240 or 360 Units are rated at 80...

Page 20: ...Indoor Coil Type Tube Size in Face Area sq ft Rows FPI Refrigerant Control Drain Connection Number Size in Hi Performance 0 375 26 00 3 15 Short Orifice 1 1 00 NPT Outdoor Fan Type Number Used Diamet...

Page 21: ...I conditions and in accordance with ARI Standard 210 240 or 360 iv Integrated Part Load Value is rated in accordance with ARI Standard 210 240 or 360 Units are rated at 80 F ambient 80 F entering dry...

Page 22: ...15 Short Orifice 1 1 00 NPT Hi Performance 0 375 26 00 3 15 Short Orifice 1 1 00 NPT Outdoor Fan Type Number Used Diameter in Drive Type No Speeds CFM Number Motors HP Motor RPM Propeller 2 26 Direct...

Page 23: ...Units are suitable for operation to 20 of nominal cfm Certified in accordance with the Unitary Large Equipment Certification Program which is based on ARI Standard 340 360 93 iv EER is rated at ARI c...

Page 24: ...5 Short Orifice 1 1 0 NPT Hi Performance 0 375 26 00 4 vi 15 Short Orifice 1 1 0 NPT Hi Performance 0 375 26 00 4 15 Short Orifice 1 1 0 NPT Outdoor Fan Type Number Used Diameter in Drive Type No Spee...

Page 25: ...an motor heat Units are suitable for operation to 20 of nominal cfm Certified in accordance with the Unitary Large Equipment Certification Program which is based on ARI Standard 340 360 93 iii EER is...

Page 26: ...apacity 3 SHC Sensible Heat Capacity Indicates both downflow and horizontal units Table 7 Gross Cooling Capacities 15 Tons Three Phase Standard Efficiency T YC 180B3 4 W K Ambient Temperature 85 95 10...

Page 27: ...MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Indicates both downflow and horizontal units Table 9 Gross Cooling Capacities 20 Tons Three Phase Standard Efficiency T YC 240B3 4 W K Ambient Te...

Page 28: ...197 249 249 253 248 285 192 90 308 308 310 309 329 239 297 297 297 297 318 240 284 284 284 284 304 239 268 268 268 268 286 235 10500 75 275 243 305 183 323 122 256 233 291 177 314 117 236 223 273 188...

Page 29: ...0 163 0 160 0 172 0 121 0 157 0 157 0 157 0 157 0 168 0 122 0 151 0 151 0 151 0 151 0 163 0 123 0 143 0 143 0 143 0 143 0 155 0 122 0 5500 75 145 0 129 0 161 0 95 8 168 0 62 6 134 0 124 0 156 0 94 4 1...

Page 30: ...9 0 131 9 176 3 105 6 143 1 143 1 151 6 128 2 168 2 101 9 136 7 136 7 143 6 124 2 159 8 98 2 129 9 129 9 135 2 120 1 150 7 94 2 90 157 2 157 2 160 1 153 3 176 4 126 4 151 1 151 1 151 1 151 1 168 3 122...

Page 31: ...3 173 197 127 162 162 162 162 186 124 90 201 201 200 200 214 153 194 194 195 194 208 155 185 185 185 185 199 154 175 175 175 175 187 152 6600 75 181 162 198 123 208 76 6 168 155 191 117 204 74 4 152 1...

Page 32: ...180 1 193 9 158 1 215 3 127 3 173 8 173 8 185 8 154 0 206 3 123 2 167 0 167 0 177 2 149 7 196 8 119 0 159 9 159 9 168 2 145 3 186 9 114 7 90 189 8 189 8 189 8 189 8 215 5 151 6 183 3 183 3 183 3 183...

Page 33: ...32 0 233 0 230 0 244 0 173 0 227 0 227 0 227 0 227 0 241 0 180 0 218 0 218 0 218 0 218 0 232 0 182 0 205 0 205 0 204 0 204 0 221 0 181 0 7700 75 210 0 190 0 228 0 138 0 235 0 88 9 195 0 183 0 222 0 13...

Page 34: ...227 5 191 5 250 9 150 9 206 7 206 7 217 4 186 6 239 8 146 1 198 1 198 1 207 2 181 8 228 5 141 3 189 1 189 1 196 3 176 6 216 5 136 2 90 226 3 226 3 226 2 226 2 251 4 182 3 218 0 218 0 221 1 212 1 240 4...

Page 35: ...55 237 278 177 230 230 232 226 266 177 90 280 280 282 273 295 205 274 274 274 274 291 212 264 264 264 264 280 214 250 250 248 248 267 218 8800 75 258 230 278 167 287 109 240 221 270 164 284 105 219 21...

Page 36: ...7 267 4 227 6 295 7 181 1 244 3 244 3 255 7 221 6 282 7 175 3 234 3 234 3 243 5 215 5 269 1 169 3 223 6 223 6 230 6 209 1 254 6 163 1 90 267 6 267 6 270 3 265 1 296 0 217 7 257 9 257 9 257 8 257 8 28...

Page 37: ...3 85 240 3 240 3 256 9 213 7 285 5 172 0 231 1 231 1 245 4 207 5 272 7 165 9 221 4 221 4 233 3 201 2 259 4 159 7 211 2 211 2 220 8 194 7 245 5 153 3 90 254 0 254 0 259 2 248 5 286 0 206 7 244 5 244 5...

Page 38: ...284 312 208 267 267 267 267 297 208 90 318 318 318 318 331 241 312 312 312 312 324 248 301 301 301 301 314 255 287 287 287 287 299 257 10500 75 286 265 311 190 320 122 267 256 300 189 316 118 247 246...

Page 39: ...1 305 6 274 3 337 2 215 2 283 4 283 4 291 5 267 1 321 4 208 1 271 0 271 0 276 9 259 7 304 9 200 7 258 0 258 0 261 9 252 2 287 8 193 1 90 311 9 311 9 311 8 311 8 338 0 261 8 299 6 299 6 299 6 299 6 32...

Page 40: ...43 911 2 56 935 2 67 960 2 79 983 2 90 1005 3 02 1028 3 13 5000 830 2 48 856 2 62 882 2 76 907 2 89 931 3 02 955 3 16 977 3 30 1001 3 44 1022 3 56 1045 3 70 5500 861 2 93 884 3 10 906 3 25 930 3 41 9...

Page 41: ...03 3 05 1025 3 18 1049 3 32 5000 847 2 56 873 2 70 897 2 83 921 2 96 945 3 09 970 3 24 993 3 38 1017 3 53 1041 3 69 1064 3 85 5500 881 3 06 903 3 22 926 3 37 948 3 52 971 3 67 993 3 80 1015 3 95 1036...

Page 42: ...9 2 30 844 2 43 871 2 57 898 2 70 923 2 83 946 2 96 970 3 09 994 3 23 1018 3 39 1041 3 54 5400 855 2 84 878 3 00 901 3 15 923 3 29 945 3 43 969 3 58 993 3 73 1016 3 88 1038 4 03 1060 4 17 6000 894 3 4...

Page 43: ...3 19 1011 3 34 1034 3 49 1057 3 65 5200 861 2 76 885 2 90 908 3 04 932 3 18 955 3 31 978 3 46 1002 3 60 1025 3 75 1047 3 90 1070 4 06 5600 888 3 17 910 3 33 932 3 49 954 3 64 976 3 79 998 3 93 1020 4...

Page 44: ...21 1033 4 39 1056 4 58 1078 4 77 1099 4 96 1122 5 18 6300 976 4 46 997 4 63 1019 4 82 1040 5 00 1060 5 19 1079 5 39 1100 5 60 1118 5 79 1138 6 00 1157 6 20 7000 1039 5 65 1057 5 82 1074 6 00 1092 6 19...

Page 45: ...4 27 1039 4 45 1060 4 62 1082 4 81 1105 5 01 1127 5 22 6300 984 4 53 1005 4 70 1026 4 88 1047 5 07 1067 5 27 1087 5 46 1106 5 66 1125 5 86 1145 6 07 1164 6 27 7000 1049 5 74 1066 5 92 1084 6 11 1102 6...

Page 46: ...20 1 30 1 40 1 50 1 60 1 70 1 80 1 90 2 00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor Sheaves 5 HP Standard Motor High Static Drive Accesso...

Page 47: ...essure Inches of Water 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 90 2 00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor Drive 5 HP Standard Mot...

Page 48: ...rence Table 50 For Standard Motor Low Static Drive Accessory Fan Speed RPM reference Table 51 For Oversized Evaporator Fan Speed RPM reference Table 53 Fan motor heat MBH 3 15 x Fan BHP Notes Data inc...

Page 49: ...eference Table 50 For Standard Motor Low Static Drive Accessory Fan Speed RPM reference Table 51 For Oversized Evaporator Fan Speed RPM reference Table 53 Fan motor heat MBH 3 15 x Fan BHP Notes Data...

Page 50: ...1 3250 798 1 52 827 1 64 853 1 76 880 1 88 905 2 01 928 2 13 953 2 26 976 2 38 998 2 51 1020 2 63 4000 839 2 07 867 2 21 893 2 33 919 2 47 943 2 59 967 2 73 991 2 88 1013 3 03 1036 3 18 1056 4 3 33 45...

Page 51: ...842 1 73 869 1 85 895 1 98 920 2 11 945 2 24 968 2 38 991 2 51 1014 2 65 1035 2 79 1057 2 94 3500 885 2 17 910 2 31 935 2 45 959 2 59 983 2 74 1006 2 89 1029 3 04 1051 3 19 1072 3 34 1093 3 49 4000 93...

Page 52: ...Standard Motor High Static Drive Accessory 4000 740 2 07 766 2 23 791 2 38 814 2 54 838 2 70 860 2 86 883 3 02 905 3 19 926 3 37 948 3 55 4500 763 2 44 787 2 61 811 2 78 835 2 96 858 3 13 880 3 31 90...

Page 53: ...3 HP Standard Motor Drive 3 HP Standard Motor High Static Drive Accessory 4000 841 2 09 869 2 23 896 2 36 922 2 50 947 2 63 971 2 76 994 2 89 1016 3 04 1037 3 19 1059 3 35 4500 869 2 52 896 2 68 923...

Page 54: ...ersized Motor Drive 4000 940 2 56 964 2 71 987 2 86 1011 3 01 1034 3 16 1056 3 32 1077 3 47 1098 3 62 1120 3 79 1140 3 95 4500 994 3 16 1016 3 32 1038 3 49 1059 3 66 1080 3 83 1102 4 00 1122 4 17 1143...

Page 55: ...dard Motor Drive 3 HP Standard Motor High Static Drive 4000 746 2 10 771 2 26 795 2 41 819 2 57 842 2 72 864 2 89 886 3 05 908 3 22 929 3 40 951 3 58 4500 770 2 49 794 2 66 818 2 83 841 3 01 863 3 18...

Page 56: ...2 47 845 2 63 864 2 80 3900 688 1 84 715 2 00 741 2 17 766 2 34 790 2 51 812 2 68 834 2 85 855 3 03 875 3 21 895 3 39 4800 710 2 29 735 2 48 760 2 68 785 2 88 809 3 09 832 3 29 854 3 49 876 3 69 898...

Page 57: ...Motor High Static Drive Accessory 3000 646 1 43 669 1 56 692 1 70 714 1 84 734 1 98 755 2 13 775 2 28 793 2 42 813 2 58 830 2 72 3600 669 1 72 694 1 88 716 2 02 738 2 18 759 2 34 778 2 49 798 2 66 81...

Page 58: ...HP RPM BHP RPM BHP 3 HP Standard Motor Drive 3 HP Standard Motor High Static Drive Accessory 4800 719 2 36 744 2 55 769 2 75 792 2 95 815 3 14 838 3 34 859 3 54 880 3 73 901 3 93 921 4 13 5400 742 2 7...

Page 59: ...HP RPM BHP RPM BHP RPM BHP 3 HP Standard Motor Drive 3 HP Standard Motor High Static Drive Accessory 4800 719 2 49 742 2 69 765 2 89 787 3 09 808 3 28 829 3 48 849 3 68 869 3 89 887 4 09 906 4 29 5400...

Page 60: ...1 95 756 2 11 779 2 27 801 2 43 822 2 60 843 2 77 863 2 94 882 3 11 4550 703 2 15 729 2 34 754 2 54 779 2 73 803 2 92 827 3 11 849 3 31 871 3 50 892 3 70 913 3 89 5600 736 2 83 761 3 03 785 3 23 807 3...

Page 61: ...RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor Drive 5 HP Standard Motor High Static Drive Accessory 5600 749 2 93 773 3 13 796 3 33 818 3 54 840 3 75 861 3 98 882 4 20 903 4 43 923 4 66 943 4 8...

Page 62: ...PM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor Drive 5 HP Standard Motor High Static Drive Accessory 4000 688 1 87 714 2 03 739 2 20 764 2 36 787 2 53 810 2 70 831 2 87 852 3 05 873 3 23 8...

Page 63: ...P 5 HP Standard Motor Drive 5 HP Standard Motor High Static Drive 4000 684 1 94 708 2 10 731 2 27 753 2 43 775 2 60 795 2 77 814 2 94 834 3 12 852 3 29 870 3 47 4800 711 2 44 735 2 63 758 2 81 780 3 0...

Page 64: ...40 1 50 1 60 1 70 1 80 1 90 2 00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor Drive 5 HP Standard Motor High Static Drive Accessory 6400 779...

Page 65: ...50 1 60 1 70 1 80 1 90 2 00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5 HP Standard Motor Drive 5 HP Standard Motor High Static Drive Accessory 6400 789 3 88...

Page 66: ...tor Low Static Drive Accessory Fan Speed RPM reference Table 51 For Oversized Evaporator Fan Speed RPM reference Table 53 Fan motor heat MBH 3 15 x Fan BHP Notes Data includes pressure drop due to sta...

Page 67: ...ued For Standard Evaporator Fan Speed RPM reference Table 50 For Standard Motor Low Static Drive Accessory Fan Speed RPM reference Table 51 For Oversized Evaporator Fan Speed RPM reference Table Table...

Page 68: ...Open Open Open Open Open Closed 17 T YC 210C3 4 W 705 755 806 856 907 957 N A 25 T YC 300B3 4 W 301C3 4 W 594 631 668 705 742 779 N A Table 52 Standard Motor High Static Drive Accessory Sheave Fan Spe...

Page 69: ...09 15 T YC 180B 4800 0 07 0 10 0 25 0 03 0 04 0 04 0 05 6000 0 10 0 15 0 33 0 04 0 06 0 07 0 08 7200 0 15 0 19 0 40 0 05 0 09 0 10 0 12 T YCD181C 3000 0 02 0 01 0 03 0 07 0 03 4800 0 04 0 02 0 07 0 14...

Page 70: ...240v 380v 480v and 600v For other than rated voltage CAP voltage rated voltage 2 x rated cap Stage1 Stage 2 Unit Model kW MBH No of kW MBH kW MBH Tons Number Input ii ii For all input output categorie...

Page 71: ...eheat option Leaving Evaporator Dry Bulb F iii iii Temperature does not account for indoor fan heat Tons SCFM 35 40 45 50 55 60 65 12 2500 23 4 23 8 25 0 26 9 29 5 32 9 37 0 3000 21 4 21 6 22 5 24 0 2...

Page 72: ...al number of remote sensors to obtain space temperature averaging This sensor should be utilized with ReliaTel controls Economizer Controls The standard equipment offering is a fixed dry bulb changeov...

Page 73: ...ortless set up Program each day separately with no need to copy multiple days All programming can be done on one screen Easy to read and use Large clear backlit digital display Digital Display Program...

Page 74: ...Maximum Circuit Breaker 12 T YC 150D3 187 253 63 80 69 80 T YC 150D4 414 506 33 40 36 40 T YC 150DW 518 633 26 30 28 35 T YC 150DK 342 418 43 50 15 T YC 180B3 187 253 78 90 84 100 T YC 180B4 414 506...

Page 75: ...RL354A AYHHTRN354A 40 5 54 0 2 171 193 175 200 AYDHTRK372A AYHHTRN372A 54 0 72 0 2 218 247 225 250 460 Volts Three Phase 12 TC 150D4 AYDHTRL418A AYHHTRN418A 18 0 1 34 40 37 40 AYDHTRK436A AYHHTRN436A...

Page 76: ...del Number No Volts Phase HP ii ii HP for each compressor RPM RLA LRA No Phase HP FLA LRA 12 T YC 150D3 2 208 230 3 6 00 3450 20 4 156 2 1 50 3 2 8 8 T YC 150D4 2 460 3 6 00 3450 10 8 75 2 1 50 1 6 3...

Page 77: ...3 7 50 11 0 74 0 T YC 210CW 1 575 3 5 00 6 1 41 6 1 575 3 7 50 9 0 60 0 T YC 210CK 1 380 3 7 5 13 3 83 5 20 T YC 240B3 1 208 230 3 5 00 16 7 109 8 1 208 230 3 7 50 24 2 120 4 T YC 240B4 1 460 3 5 00...

Page 78: ...ity i i For Standard and Oversized Indoor Fan Motor values do not include power exhaust accessory Maximum Fuse Size or Maximum Circuit Breaker Minimum Circuit Ampacity Maximum Fuse Size or Maximum Cir...

Page 79: ...3 175 200 AYDHTRK372A AYHHTRN372A 54 0 72 0 2 218 247 225 250 460 Volts Three Phase 12 TC 151C4 AYDHTRL418A AYHHTRN418A 18 0 1 34 40 37 40 AYDHTRK436A AYHHTRP436A 36 0 2 61 70 64 70 AYDHTRK454A AYHHTR...

Page 80: ...HTRK372A 54 0 72 0 2 209 238 225 250 218 247 225 250 25 TCD301C3 AYDHTRL336A 27 0 36 0 2 125 139 150 150 AYDHTRL354A 40 5 54 0 2 171 193 175 200 AYDHTRK372A 54 0 72 0 2 218 247 225 250 460 Volts Three...

Page 81: ...113 2 1 1 00 2 9 9 3 T YC 241CW 2 575 3 9 30 3450 12 9 85 2 1 1 00 2 0 5 7 25 T YC 301C3 2 208 230 3 10 00 3450 37 6 278 2 1 1 00 5 5 18 3 T YC 301C4 2 460 3 10 00 3450 18 3 124 2 1 1 00 2 9 9 3 T YC...

Page 82: ...amps Amps Tons Unit Model Number No Volts Phase HP ii ii HP for each compressor Indicates downflow and horizontal units FLA LRA No Volts Phase HP FLA LRA 12 T YC 151C3 1 208 230 3 3 00 10 6 81 0 1 20...

Page 83: ...ire three phase 2 Power Wires 1 Ground Wire single phase For specific wiring information see the installation instructions All wiring except power wire is low voltage All customer supplied wiring to b...

Page 84: ...84 RT PRC024 EN Figure 3 12 5 25 Tons Cooling with Optional Electric Heat Typical Wiring...

Page 85: ...T PRC024 EN 85 Typical Wiring 12 25 Tons Cooling with Optional Electric Heat Figure 3 continued from previous page 12 5 25 Tons Cooling with Optional Electric Heat for specific wiring see service fact...

Page 86: ...86 RT PRC024 EN Typical Wiring 12 25 Tons Cooling with Optional Electric Heat Figure 4 12 5 25 Tons Cooling with Optional Electric Heat for specific wiring see service facts...

Page 87: ...T PRC024 EN 87 Typical Wiring 12 25 Tons Cooling with Optional Electric Heat Figure 4 continued from previous page 12 5 25 Tons Cooling with Optional Electric Heat for specific wiring see service fact...

Page 88: ...88 RT PRC024 EN Typical Wiring 12 25 Tons Gas Electric Figure 5 12 5 25 Tons Gas Electric for specific wiring see service facts...

Page 89: ...RT PRC024 EN 89 Typical Wiring 12 25 Tons Gas Electric Figure 5 continued from previous page 12 5 25 Tons Gas Electric for specific wiring see service facts...

Page 90: ...90 RT PRC024 EN Typical Wiring 12 25 Tons Gas Electric Figure 6 12 5 25 Tons Gas Electric for specific wiring see service facts...

Page 91: ...RT PRC024 EN 91 Typical Wiring 12 25 Tons Gas Electric Figure 6 continued from previous page 12 5 25 Tons Gas Electric for specific wiring see service facts...

Page 92: ...s millimeters 1 2 NPT Gas Connection Y_C Models only 2 Electrical Connection Single Point Power When Heat Installed T_C Models only Figure 8 Cooling with Optional Electric Heat and Gas Electric Models...

Page 93: ...ctric Models 12 17 Tons Standard Efficiency 12 High Efficiency Downflow Duct Connections Field Fabricated Duct flanges mount 7 7 16 189mm down inside the curb on the 1 5 38mm curb flanges Roofcurb is...

Page 94: ...els 20 25 Tons Standard Efficiency 15 25 Tons High Efficiency All dimensions are in inches millimeters Figure 13 Cooling with Optional Electric Heat and Gas Electric Models 20 25 Tons Standard Efficie...

Page 95: ...Heat and Gas Electric Models 20 25 Tons Standard Efficiency 15 25 Tons High Efficiency Downflow Duct Connections Field Fabricated Duct flanges mount 7 7 16 down inside the curb on the 1 1 curb flange...

Page 96: ...1 16 4 1 4 4 1 4 62 7 16 54 11 16 1 NPT 25 5 8 6 20 25 26 7 16 28 3 4 19 15 16 4 1 4 4 1 4 76 5 16 68 11 16 1 NPT 26 3 4 5 3 8 Table 79 High Efficiency Units Cooling and Gas Electric Condensate Conden...

Page 97: ...it Swing Diameter Through the Base Electrical Height of Gas Pipe Second Drawing SWING RADIUS C OD SECTION ACCESS PANEL THROUGH THE BASE ELECTRICAL SWING RADIUS A ID SECTION ACCESS PANEL TOP VIEW SHOWI...

Page 98: ...haust Downflow Economizers Side View Unit Model A B i i Horizontal dimension only Downflow economizer is width of end panel C ii ii Power exhaust is applied on downflow economizer only T YC 150 151 18...

Page 99: ...10 2051 702 533 353 463 53 34 25 TC 300B TC 301C 2365 2475 1906 2016 661 695 507 524 320 343 418 454 53 53 33 34 Table 84 Maximum Unit Corner Weights Lbs and Center of Gravity Dimensions in Gas Electr...

Page 100: ...210C T YCH151C 50 32 60 5 2 2 5 T YCH240B T YCH181 211 241C 65 32 75 5 2 5 T YCH300B 301C 65 32 75 N A N A 2 5 Table 86 continued Accessory Net Weights Lbs Electric Heaters Unit All 6 23 kW 27 36 kW...

Page 101: ...YC 150 181 oversize motor 0 T YC 210 241 oversize motor T YC 300 301 standard size motor Hinged Doors 27 All T YC units Powered Convenience Outlet 38 All T YC units Through the Base Electrical 23 All...

Page 102: ...All models shall have crankcase heaters low and high pressure control as standard Crankcase Heaters These band heaters provide improved compressor reliability by warming the oil to prevent migration d...

Page 103: ...ed from the line side of the disconnect or circuit breaker and therefore will not be affected by the position of the disconnect or circuit breaker This option can only be ordered when the Through the...

Page 104: ...ith an Electric Heater the heater must be factory installed Frostat This option is to be utilized as a safety device The Frostat opens when temperatures on the evaporator coil fall below 10 F The temp...

Page 105: ...it and provide support and a water tight installation when installed properly The roof curb design shall allow field fabricated rectangular supply return ductwork to be connected directly to the curb...

Page 106: ......

Page 107: ......

Page 108: ...your local Trane office or e mail us at comfort trane com Literature Order Number RT PRC024 EN Date May 2007 Supersedes RT PRC024 EN December 2006 Trane has a policy of continuous product and product...

Reviews: