78
RT-PRC024-EN
Electrical Data
(High Efficiency)
Table 66. Unit Wiring with Cooling (No Electric Heat) or Gas Heat — Standard Refrigeration System
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Tons
Unit Model
Number
Unit Operating
Voltage Range
Minimum Circuit
Ampacity
(i)
(i)
For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
*
Indicates both downflow and horizontal units.
Maximum Fuse
Size or Maximum
Circuit Breaker
Minimum Circuit
Ampacity
Maximum Fuse
Size or Maximum
Circuit Breaker
12½
T/YC*151C3
187-253
64
80
70
90
T/YC*151C4
414-506
31
40
34
40
T/YC*151CW
517-633
25
30
28
35
15
T/YC*181C3
187-253
74
90
80
100
T/YC*181C4
414-506
36
50
38
50
T/YC*181CW
517-633
29
40
31
40
17½
T/YC*211C3
187-253
91
110
98
125
T/YC*211C4
414-506
44
60
48
60
T/YC*211CW
517-633
35
45
38
50
20
T/YC*241C3
187-253
99 125 107
125
T/YC*241C4
414-506
50
60
54
60
T/YC*241CW
517-633
40
50
43
50
25
T/YC*301C3
187-253
120
150
N/A
N/A
T/YC*301C4
414-506
58
70
N/A
N/A
T/YC*301CW
517-633
47
60
N/A
N/A
Table 67.
Unit Wiring with Cooling (No Electric Heat) or Gas Heat — TXV/Face-Split Evaporator Coil (Downflow Only)
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Tons
Unit Model
Number
Unit Operating
Voltage Range
Minimum Circuit
Ampacity
(i)
(i)
For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
Maximum Fuse Size or
Maximum Circuit
Breaker
Minimum Circuit
Ampacity
Maximum Fuse Size or
Maximum Circuit
Breaker
12½
T/YCD151C3
187-253
59
70
65
80
T/YCD151C4
414-506
30
35
32
40
T/YCD151CW
517-633
24
30
26
30
15
T/YCD181C3
187-253
74
90
80
90
T/YCD181C4
414-506
37
50
39
50
T/YCD181CW
517-633
30
40
32
40
17½
T/YCD211C3
187-253
91
125
99
125
T/YCD211C4
414-506
45
60
49
60
T/YCD211CW
517-633
36
45
39
50
20
T/YCD241C3
187-253
99
125
107
125
T/YCD241C4
414-506
51
60
54
60
T/YCD241CW
517-633
40
50
43
50
25
T/YCD301C3
187-253
117
150
N/A
N/A
T/YCD301C4
414-506
57
70
N/A
N/A
T/YCD301CW
517-633
46
50
N/A
N/A
Table 68. Unit Wiring with Cooling (No Electric Heat) or Gas Heat — Dehumidification (Hot Gas Reheat) Option
(Downflow Only)
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Tons
Unit Model
Number
Unit Operating
Voltage Range
Minimum Circuit
Ampacity
(i)
(i)
For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
Maximum Fuse Size or
Maximum Circuit
Breaker
Minimum Circuit
Ampacity
Maximum Fuse Size or
Maximum Circuit
Breaker
12½
T/YCD151C3
187-253
59
70
65
80
T/YCD151C4
414-506
30
35
32
40
T/YCD151CW
517-633
24
30
26
30
15
T/YCD181C3
187-253
71
90
77
100
T/YCD181C4
414-506
36
45
39
50
T/YCD181CW
517-633
28
35
30
40
20
T/YCD241C3
187-253
98
125
105
125
T/YCD241C4
414-506
50
60
53
60
T/YCD241CW
517-633
39
50
42
50