74
RT-PRC024-EN
Table 60. Unit Wiring with Gas Heat or Cooling (No Electric Heat)
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Tons
Unit Model
Number
Unit Operating
Voltage Range
Minimum Circuit
Ampacity
(i)
(i)
For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
*
Indicates both downflow and horizontal units.
Maximum Fuse
Size or Maximum
Circuit Breaker
Minimum Circuit
Ampacity
Maximum Fuse
Size or Maximum
Circuit Breaker
12½ T/YC*150D3
187-253
63
80
69
80
T/YC*150D4
414-506
33
40
36
40
T/YC*150DW
518-633
26
30
28
35
T/YC*150DK
342-418
43
50
—
—
15
T/YC*180B3
187-253
78
90
84
100
T/YC*180B4
414-506
39
50
42
50
T/YC*180BW
517-633
31
40
33
40
T/YC*180BK
342-418
50
60
—
—
17½ T/YC*210C3
187-253
88
100
96
125
T/YC*210C4
414-506
44
50
47
60
T/YC*210CW
517-633
35
45
38
45
T/YC*210CK
342-418
57
70
—
—
20
T/YC*240B3
187-253
100 125
107
125
T/YC*240B4
414-506
50
60
54
60
T/YC*240BW
517-633
40
45
43
50
T/YC*240BK
342-418
65
80
—
—
25
T/YC*300B3
187-253
118 150 —
—
T/YC*300B4
414-506
58
70
—
—
T/YC*300BW
517-633
46
50
—
—
T/YC*300BK
342-418
70
80
—
—
Electrical Data