44
RT-PRC024-EN
Performance Data
(17½ Tons Standard Efficiency)
Table 26. Evaporator Fan Performance 17½ Tons TC*210C Downflow or Horizontal
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5-HP Standard Motor with Low Static Drive Accessory
5-HP Standard Motor & Sheaves
5600
—
—
—
—
735
2.34
759
2.46
783
2.60
807
2.74
830
2.89
852
3.03
875
3.18
898
3.33
6300
765 2.96
788
3.10
810
3.23
831
3.36
852
3.50
874
3.65
895
3.81
917
3.97
937
4.13
956
4.29
7000
845 4.02
866
4.18
886
4.33
906
4.48
925
4.62
944
4.77
963
4.93
982
5.10 1002 5.29 1021
5.47
7700
925 5.32
944
5.49
963
5.66
982
5.82
999
5.98 1016 6.14 1033 6.30 1050 6.47 1069 6.66 1086
6.86
8400 1006 6.87 1024 7.06 1041 7.24
1058 7.42 1075 7.60 1091 7.78 1107 7.95 1122 8.13 1138 8.31 1154
8.50
7.5-HP Oversized Motor & Sheaves
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5-HP Standard Motor & Sheaves
5600
923 3.50
946
3.68
968
3.85
989
4.03 1011 4.21 1033 4.39 1056 4.58 1078 4.77 1099 4.96 1122
5.18
6300
976 4.46
997
4.63 1019 4.82
1040 5.00 1060 5.19 1079 5.39 1100 5.60 1118 5.79 1138 6.00 1157
6.20
7000 1039 5.65 1057 5.82 1074 6.00
1092 6.19 1111 6.39 1130 6.59 1150 6.80 1168 7.01 1186 7.22 1205
7.46
7700 1104 7.06 1122 7.26 1138 7.46
1154 7.66 1170 7.84 1186 8.05 1202 8.25 1220 8.47
—
—
—
—
8400
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5-HP Oversized Motor Sheaves
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference
Table 51
.
For Oversized Evaporator Fan Speed (RPM), reference
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
*For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to "Motor & Sheave/Fan Speed" tables to determine operating range.