RT-PRC024-EN
67
Performance Data
(25 Tons High Efficiency)
Table 49. Evaporator Fan Performance 25 Tons with Gas Heat YC*301C Standard Refrigeration or TXV System Downflow or
Horizontal
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Low Static Drive Accessory
7.5-HP Standard Motor Drive
8000
643
3.29
670
3.54
695
3.79
718
4.01
739
4.21
759
4.41
778
4.61
798
4.82
817
5.04
837
5.27
8500
680
3.92
705
4.18
729
4.44
752
4.69
772
4.92
792
5.13
810
5.33
829
5.55
847
5.77
865
6.00
9000
717
4.61
741
4.89
764
5.17
786
5.44
806
5.69
825
5.92
843
6.14
861
6.36
878
6.59
895
6.83
9500
754
5.39
777
5.68
799
5.98
820
6.27
840
6.55
859
6.80
876
7.04
893
7.27
910
7.50
926
7.74
10000 791
6.26
813
6.56
835
9.87
855
7.18
874
7.48
893
7.76
910
8.02
926
8.27
942
8.51
—
—
10500 828
7.21
850
7.52
870
7.85
890
8.18
909
8.50
—
—
—
—
—
—
—
—
—
—
11000 866
8.26
886
8.59
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & High Static Drive Accessory
Continued
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Standard Motor & Low Static Drive Accessory Fan Speed
(RPM), reference
Table 51
.
For Oversized Evaporator Fan Speed (RPM), reference Table
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure
drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Drive
8000
857
5.51
876
5.76
896
6.01
815
6.26
933
6.51
8500
884
6.24
903
6.50
921
6.76
940
7.03
958
7.30
9000
913
7.07
930
7.32
948
7.59
965
7.86
983
8.15
9500
943
7.99
959
8.25
976
8.51
—
—
—
—
10000
—
—
—
—
—
—
—
—
—
—
10500
—
—
—
—
—
—
—
—
—
—
11000
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & High Static Drive Accessory
Summary of Contents for Voyager TC Series
Page 84: ...84 RT PRC024 EN Figure 3 12 5 25 Tons Cooling with Optional Electric Heat Typical Wiring...
Page 106: ......
Page 107: ......