82
RT-PRC024-EN
Electrical Data
Table 73. Electrical Characteristics — Compressor Motor and Condenser Motor — 60 Cycle — Dehumidification (Hot Gas Reheat)
Option (Downflow Only)
Compressor Motors
Condenser Fan Motors
Amps
(i)
(i)
For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
Amps
Tons
Unit Model
Number
No.
Volts
Phase
HP
(ii)
(ii)
HP for each compressor.
RPM
RLA
LRA
No.
Phase
HP
FLA
LRA
12½
T/YCD151C3
2 208-230
3
5.7/5.7
3450
18.6
156
2
1
.50
3.2
8.8
T/YCD151C4
2
460
3
5.7/5.7
3450
9.7
75
2
1
.50
1.6
3.8
T/YCD151CW
2
575
3
5.7/5.7
3450
7.6
54
2
1
.50
1.3
3.2
15
T/YCD181C3
2 208-230
3
8.3/5.7
3450
27.4/19.0
208/156
2
1
.50
3.2
8.8
T/YCD181C4
2
460
3
8.3/5.7
3450
13.8/10.1
100/75 2
1
.50
1.6
3.8
T/YCD181CW
2
575
3
8.3/5.7
3450
10.7/7.9
68/54
2
1
.50
1.3
3.2
20
T/YCD241C3
2 208-230
3
9.0/9.3
3500/3450
30.1/31.7
225/253
2
1
1.00
5.5
18.3
T/YCD241C4
2
460
3
9.0/9.3
3500/3450
15.6/16.2
114/113
2
1
1.00
2.9
9.3
T/YCD241CW
2
575
3
9.0/9.3
3500/3450
12.1/13.0
80/85
2
1
1.00
2.0
5.7
Table 74. Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized
Standard Evaporator Fan Motor
Oversized Evaporator Fan Motor
Amps
(i)
(i)
For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
Amps
Tons
Unit Model
Number
No.
Volts
Phase
HP
(ii)
(ii)
HP for each compressor.
*
Indicates downflow and horizontal units.
FLA
LRA
No.
Volts
Phase
HP
FLA
LRA
12½
T/YC*151C3
1 208-230
3
3.00
10.6
81.0
1
208-230
3
5.00
16.7
109.8
T/YC*151C4
1
460
3
3.00
4.8
40.5
1
460
3
5.00
7.6
54.9
T/YC*151CW
1
575
3
3.00
3.9
31.0
1
575
3
5.00
6.1
41.6
15
T/YC*181C3
1 208-230
3
3.00
10.6
81.0
1
208-230
3
5.00
16.7
109.8
T/YC*181C4
1
460
3
3.00
4.8
40.5
1
460
3
5.00
7.6
54.9
T/YC*181CW
1
575
3
3.00
3.9
31.0
1
575
3
5.00
6.1
41.6
17½
T/YC*211C3
1 208-230
3
5.00
16.7
109.8
1
208-230
3
7.50
24.2
120.4
T/YC*211C4
1
460
3
5.00
7.6
54.9
1
460
3
7.50
11.0
74.0
T/YC*211CW
1
575
3
5.00
6.1
41.6
1
575
3
7.50
9.0
60.0
20
T/YC*241C3
1 208-230
3
5.00
16.7
109.8
1
208-230
3
7.50
24.2
120.4
T/YC*241C4
1
460
3
5.00
7.6
54.9
1
460
3
7.50
11.0
74.0
T/YC*241CW
1
575
3
5.00
6.1
41.6
1
575
3
7.50
9.0
60.0
25
T/YC*301C3
1 208-230
3
7.50
24.2
120.4
—
—
—
—
—
—
T/YC*301C4
1
460
3
7.50
11.0
74.0
—
—
—
—
—
—
T/YC*301CW
1
575
3
7.50
9.0
60.0
—
—
—
—
—
—
Table 75. Electrical Characteristics — Combustion Blower Motor (Gas/Electric)
Amps
Unit Model
Number
Heat
Heating
Stages
HP
RPM
(i)
(i)
High/Low Speed.
*
Indicates both downflow and horizontal units.
Volts
Phase
FLA
LRA
YC*151
Low
2
1/20
3500/2800
208-230
1
0.5
0.78
YC*181, 211, 241-301
Low
2
1/10
3500/2800
208-230
1
0.8
2.00
Table 76. Electrical Characteristics — Power Exhaust (Cooling and Gas/Electric)
Amps
Tons
Volts
Phase
HP
RPM
FLA
LRA
12½
208-230
1
3/4
1040
6.6
13.5
15,17½,20,25
460
1
3/4
1040
3.2
8.4
15,17½,20,25
575
1
3/4
1040
2.1
5.2
(High Efficiency)
Summary of Contents for Voyager TC Series
Page 84: ...84 RT PRC024 EN Figure 3 12 5 25 Tons Cooling with Optional Electric Heat Typical Wiring...
Page 106: ......
Page 107: ......