Performance Data
(25 Tons Standard Efficiency)
Table 30. Evaporator Fan Performance 25 Tons TC*300B Downflow or Horizontal
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Low Static Drive Accessory
7.5-HP Standard Motor & Sheaves
7000
—
—
—
—
593
2.42
619
2.62
643
2.80
667
2.98
690
3.16
712
3.35
733
3.53
754
3.73
7500
—
—
595
2.66
624
2.88
649
3.10
673
3.31
695
3.50
717
3.68
738
3.88
759
4.08
779
4.28
8000
595
2.92
627
3.16
655
3.39
679
3.63
702
3.86
724
4.07
745
4.28
766
4.48
786
4.68
805
4.90
8500
628
3.47
659
3.73
686
3.97
710
4.23
732
4.47
754
4.71
774
4.94
794
5.15
813
5.36
832
5.58
9000
661
4.08
691
4.36
717
4.62
741
4.89
763
5.15
784
5.41
803
5.66
822
5.89
841
6.12
859
6.35
9500
695
4.76
723
5.06
749
5.34
772
5.62
794
5.90
814
6.18
833
6.45
852
6.71
870
6.95
887
7.19
10000 729
5.52
755
5.84
781
6.13
804
6.42
825
6.72
844
7.01
863
7.31
881
7.59
899
7.86
916
8.11
10500 762
6.35
788
6.69
812
7.00
835
7.31
856
7.62
875
7.93
894
8.24
911
8.54
—
—
—
—
11000 796
7.27
821
7.63
844
7.96
867
8.3
887
8.60
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & High Static Drive Accessory
Continued
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Standard Motor & Low Static Drive Accessory Fan Speed
(RPM), reference
Table 51
.
For Oversized Evaporator Fan Speed (RPM), reference
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure
drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
*For 380V/60 Hz units, the oversized motor is used as the
standard motor. Refer to "Motor & Sheave/Fan Speed" tables to
determine operating range.
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Sheaves
7000
776
3.95
798
4.18
820
4.40
841
4.62
862
4.84
7500
798
4.48
818
4.71
839
4.95
860
5.19
880
5.42
8000
824
5.11
842
5.32
860
5.55
880
5.80
899
6.06
8500
850
5.81
868
6.03
885
6.26
902
6.49
920
6.74
9000
877
6.58
894
6.81
911
7.05
928
7.29
944
7.53
9500
904
7.43
921
7.67
938
7.92
954
8.17
970
8.42
10000 933
8.36
949
8.62
—
—
—
—
—
—
10500
—
—
—
—
—
—
—
—
—
—
11000
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & High Static Drive Accessory