General Data
(12½,15 Tons High Efficiency)
Heating Performance
(x)
(Gas/Electric Only)
Heating Models
Low
High
Low
High
Heating Input (Btuh)
150,000
250,000
250,000
350,000
1st Stage (Btu)
100,000
175,000
175,000
250,000
Heating Output (Btuh)
122,000
203,000
203,000
284,000
1st Stage (Btu)
81,000
142,000
142,000
203,000
AFUE%
(xi)
Downflow/Horizontal
81.0/81.0
80.7/79.9
80.7/79.9
80.1/79.1
Steady State Efficiency%
81.0
81.0
81.0
81.0
No. Burners
1
1
1
1
No. Stages
2
2
2
2
Gas Supply Line Pressure (in w.c.)
Natural or LP (minimum/maximum)
2.5/14.0
2.5/14.0
Gas Connection Pipe Size (in.)
1/2
1/2
1/2
3/4
(i)
TXV/Face-Split Option (Downflow Only) YCD151C3,4,W (EER):11.3; (System Power kW): 12.92; (Refrigerant Control): Expansion Valve; (Refrig-
erant Charge): 13.4/12.0.
(ii)
TXV/Face-Split Option (Downflow Only) YCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrig-
erant Charge): 26.0/12.0.
(iii)
Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan
motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in
accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93.
(iv)
EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
(v)
Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and
67°F entering wet bulb at ARI rated cfm.
(vi)
Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(vii)
For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(viii)
An optional 2 inch pleated filter is also available.
(ix)
Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(x)
Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Stan-
dards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate
of 4% for each 1000 feet above sea level.
(xi)
AFUE is rated in accordance with DOE test procedures.
Table 4.
(continued) General Data — 12½-15 Tons
12½ Tons Downflow & Horizontal Units
15 Tons Downflow & Horizontal Units