46
RT-PRC024-EN
Performance Data
(20 Tons Standard Efficiency)
Table 28. Evaporator Fan Performance 20 Tons TC*240B Downflow or Horizontal
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5-HP Standard Motor with Low Static Drive
(i)
(i)
Field Supplied Fan Sheave BK190 required. Field Supplied Belt may be necessary.
5-HP Standard Motor & Sheaves
6400
—
—
514
1.69
546
1.88
574
2.05
599
2.21
624
2.37
648
2.54
671
2.71
695
2.90
720
3.11
7200
527 2.08
562
2.29
592
2.50
619
2.71
644
2.91
667
3.09
689
3.26
711
3.45
732
3.64
752
3.83
8000
578 2.79
610
3.03
639
3.26
666
3.50
690
3.73
712
3.96
733
4.16
753
4.35
773
4.55
792
4.75
8800
629 3.65
659
3.93
687
4.18
712
4.43
736
4.69
758
4.96
778
5.20
797
5.43
816
5.65
834
5.86
9600
681 4.67
709
4.99
735
5.27
759
5.54
782
5.82
804
6.11
824
6.39
843
6.67
861
6.92
878
7.16
7.5-HP Standard Motor & Sheave
(ii)
(ii)
7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 required. Field Supplied Belt may be necessary.
*For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to "Motor & Sheave/Fan Speed" tables to determine operating range.
7.5-HP Oversized Motor & Sheaves
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5-HP Standard Motor & Sheaves
5-HP Standard Motor & High Static Drive Accessory
6400
744 3.32
768
3.52
790
3.72
811
3.91
833
4.13
855
4.36
877
4.59
897
4.82
917
5.05
936
5.29
7200
773 4.04
795
4.27
817
4.50
839
4.74
860
4.96
880
5.19
898
5.41
917
5.64
937
5.88
957
6.14
8000
811 4.96
830
5.18
848
5.40
867
5.64
887
5.90
907
6.16
927
6.42
946
6.68
964
6.93
982
7.18
8800
852 6.08
869
6.30
887
6.53
904
6.77
921
7.01
938
7.26
955
7.52
973
7.81
991
8.09
—
—
9600
895 7.40
911
7.63
928
7.86
944
8.11
960
8.36
976
8.61
—
—
—
—
—
—
—
—
7.5-HP Oversized Motor & Sheaves
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference
Table 51
.
For Oversized Evaporator Fan Speed (RPM), reference
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.