RT-PRC024-EN
49
Performance Data
(25 Tons Standard Efficiency)
Table 31. Evaporator Fan Performance 25 Tons with Gas Heat YC*300B Downflow or Horizontal
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Low Static Drive Accessory
7.5-HP Standard Motor & Drive
7000
—
—
—
—
614
2.59
639
2.77
662
2.94
684
3.11
706
3.30
728
3.49
750
3.70
773
3.92
7500
—
—
621
2.85
647
3.08
671
3.29
693
3.48
715
3.66
736
3.85
756
4.05
777
4.26
797
4.47
8000
627
3.16
655
3.39
680
3.64
704
3.87
725
4.09
746
4.28
766
4.48
785
4.68
805
4.89
824
5.11
8500
662
3.76
689
4.00
714
4.26
737
4.52
758
4.76
778
4.98
797
5.18
815
5.39
834
5.61
852
5.83
9000
698
4.43
724
4.69
747
4.96
770
5.24
790
5.50
810
5.74
828
5.97
846
6.18
864
6.41
881
6.63
9500
734
5.18
758
5.45
781
5.73
803
6.02
823
6.31
842
6.58
860
6.83
878
7.06
895
7.29
911
7.53
10000 770
6.00
793
6.29
816
6.59
837
6.89
856
7.20
875
7.49
893
7.77
910
8.02
926
8.27
942
8.51
10500 806
6.92
829
7.22
850
7.53
870
7.85
890
8.17
908
8.48
—
—
—
—
—
—
—
—
11000 842
7.92
864
8.24
885
8.56
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & High Static Drive Accessory
Continued
For Standard Evaporator Fan Speed (RPM), reference
Table 50
.
For Standard Motor & Low Static Drive Accessory Fan Speed
(RPM), reference
Table 51
.
For Oversized Evaporator Fan Speed (RPM), reference
Table 53
.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure
drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
*For 380V/60 Hz units, the oversized motor is used as the
standard motor. Refer to "Motor & Sheave/Fan Speed" tables to
determine operating range.
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7.5-HP Standard Motor & Drive
7000
795
4.14
816
4.36
837
4.58
858
4.80
879
5.03
7500
818
4.70
839
4.94
859
5.18
879
5.41
899
5.65
8000
843
5.34
862
5.58
882
5.83
901
6.09
920
6.34
8500
870
6.06
888
6.30
906
6.55
924
6.81
943
7.08
9000
898
6.87
916
8.11
933
7.36
950
7.62
967
7.89
9500
928
7.77
944
8.01
960
8.27
977
8.53
—
—
10000
—
—
—
—
—
—
—
—
—
—
10500
—
—
—
—
—
—
—
—
—
—
11000
—
—
—
—
—
—
—
—
—
—
7.5-HP Standard Motor & High Static Drive Accessory
Summary of Contents for Voyager TC Series
Page 84: ...84 RT PRC024 EN Figure 3 12 5 25 Tons Cooling with Optional Electric Heat Typical Wiring...
Page 106: ......
Page 107: ......