227
Warning: Low feedback, FBLOW
Value:
-100,000.000 - par. 228
Warn.:FB HIGH
-4000.000
Function:
If the feedback signal falls below the preset limit
FBLOW, a warning is given.
Parameters 223-228
Warning functions
are out of func-
tion during ramp-up after a start command and after
a stop command or during stop. The warning func-
tions are activated when the output frequency has
reached the resulting reference.The signal outputs
can be programmed to give a warning signal via ter-
minal 46 and via the relay output.The unit for feed-
back in Closed loop is programmed in parameter 416
Process units
.
Description of choice:
Set the required value within the feedback range (pa-
rameter 414
Minimum feedback, FB MIN
and 415
Maxi-
mum feedback, FB MAX
).
228
Warning: High feedback, FBHIGH
Value:
Par. 227
Warn.: FB LOW
- 100,000.000
4000.000
Function:
If the feedback signal gets above the preset limit
FBHIGH, a warning is given.
Parameters 223-228
Warning functions
are out of func-
tion during ramp-up after a start command and after
a stop command or during stop. The warning func-
tions are activated when the output frequency has
reached the resulting reference. The signal outputs
can be programmed to give a warning signal via ter-
minal 46 and via the relay output. The unit for feed-
back in Closed loop is programmed in parameter 416
Process units
.
Description of choice:
Set the required value within the feedback range (pa-
rameter 414
Minimum feedback, FB MIN
and 415
Maxi-
mum feedback, FB MAX
).
229
Frequence bypass, bandwidth
Value:
0 (OFF) - 100 Hz
0 Hz
Function:
Some systems call for some output frequencies to be
avoided because of mechanical resonance problems
in the system. In parameters 230-231
Frequency by-
pass
these output frequencies can be programmed. In
this parameter a bandwidth can be defined on either
side of these frequencies.
Description of choice:
The frequency set in this parameter will be centered
around parameters 230
Frequency bypass 1
and 231
Frequency bypass 2
.
230
Frequency bypass 1 (FREQ. BYPASS 1)
231
Frequency bypass 2 (FREQ. BYPASS 2)
Value:
0 - 1000 Hz
0.0 Hz
Function:
Some SYSTEMs call for some output frequencies to
be avoided because of mechanical resonance prob-
lems in the SYSTEM.
Description of choice:
Enter the frequencies to be avoided. See also param-
eter 229
Frequency bypass, bandwidth
.
38
TR1
2800
Series
VFD
Programming
Summary of Contents for VarioTrane TR1 2800 Series
Page 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Page 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Page 4: ...TR1 2800 Series VFD 3...
Page 7: ...6 TR1 2800 Series VFD...
Page 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Page 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Page 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...