515-544 Data readout
Value:
Par.
no.
Description
Display
text
Unit
515
Res.
reference
(REFERENCE
%)
%
516
Res.
reference
[Unit]
(REFERENCE
[UNIT])
Hz,
rpm
517
Feedback
[Unit]
(FEEDBACK
[UNIT])
Par.
416
518
Frequency
(FREQUENCY)
Hz
519
Frequency
x
scale
(FREQUENCY
X
SCALE)
Hz
520
Motor
current
(MOTOR
CURRENT)
Amp
521
Torque
(TORQUE)
%
522
Power[kW]
(POWER
(KW))
kW
523
Power[HP]
(POWER
(HP))
HP
524
Motor
voltage
(MOTOR
VOLTAGE)
V
525
DC-link
voltage
(DC
LINK
VOLTAGE)
V
526
Thermal
load
motor
(MOTOR
THERMAL)
%
527
Thermal
load
inverter
(INV.
THERMAL)
%
528
Digital
input
(DIGITAL
INPUT)
Bin
529
Term.53,
analogue
input
(ANALOG
INPUT
53)
V
531
Term.60,
analogue
input
(ANALOG
INPUT
60)
mA
532
Pulse
reference
(PULSE
REFERENCE)
Hz
533
External
ref.
(EXT.
REF.%)
%
534
Status
word,
Hex
(STATUS
WORD)
Hex
535
Bus
feedback
1
(BUS
FEEDBACK1)
Hex
537
Inverter temperature
(INVERTER TEMP.)
°
C
538
Alarm
word
(ALARM
WORD)
Hex
539
Control
word
(CONTROL
WORD)
Hex
540
Warning
word
(WARN.
WORD)
Hex
541
Extended
status
word
(STATUS
WORD)
Hex
544
Pulse
count
(PULSE
COUNT)
Function:
These parameters can be read out via the serial com-
munication port and the LCP display. See also pa-
rameters 009-012
Display readout
.
NOTE:
Parameters 515-541 can only be read out via an LCP
control unit.
Description of choice:
Resulting reference %, parameter 515:
Gives the resulting reference as a percentage in the
range from Minimum reference, Ref MIN to Maxi-
mum reference, Ref MAX. See also
Dealing with refer-
ences
.
Resulting reference [unit], parameter 516:
Gives the resulting reference in Hz in Open loop (pa-
rameter 100). In a closed loop the reference unit is
selected in parameter 416
Process units
.
Feedback [unit], parameter 517:
Gives the resulting feedback value with the unit/scal-
ing selected in parameters 414, 415 and 416. See also
dealing with feedback.
Frequency [Hz], parameter 518:
Gives the output frequency from the frequency con-
verter.
Frequency x scaling [-], parameter 519:
corresponds to the present output frequency f M mul-
tiplied by the factor preset in parameter 008
Display
scaling of output frequency
.
Motor current [A], parameter 520:
Gives the motor's phase current measured as an ef-
fective value.
Torque [Nm], parameter 521:
Gives the motor's present load in relation to the mo-
tor's rated torque.
Power [kW], parameter 522:
Gives the present power absorbed by the motor in
kW.
Power [HP], parameter 523:
Gives the present power absorbed by the motor in
HP.
Motor voltage, parameter 524:
Gives the voltage being supplied to the motor.
DC link voltage, parameter 525:
Gives the intermediate circuit voltage in the frequen-
cy converter.
Thermal load, motor [%], parameter 526:
76
TR1
2800
Series
VFD
Programming
Summary of Contents for VarioTrane TR1 2800 Series
Page 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Page 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Page 4: ...TR1 2800 Series VFD 3...
Page 7: ...6 TR1 2800 Series VFD...
Page 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Page 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Page 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...