004
Active Setup
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup
1
(setup
1)
[1]
Setup
2
(setup
2)
[2]
Setup
3
(setup
3)
[3]
Setup
4
(setup
4)
[4]
Multi Setup (MULTI SETUP)
[5]
Function:
The active parameter Setup is selected here. All pa-
rameters can be programmed in four individual pa-
rameter Setups. Shifts between Setups can be made
in this parameter via a digital input or via serial com-
munication.
Description of choice:
Factory Setup
[0] contains the factory-set parameter
values.
Setup 1-4
[1]-[4] are four individual Setups
which can be selected as required.
Multi Setup
[5] is
used where remote-controlled shifts between the
four Setups via a digital input or via serial communi-
cation is required.
005
Programming Setup
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup
1
(setup
1)
[1]
Setup
2
(setup
2)
[2]
Setup
3
(setup
3)
[3]
Setup
4
(setup
4)
[4]
Active Setup (ACTIVE SETUP)
[5]
Function:
You can select which Setup you want to programme
during operation (applies both via the control panel
and the serial communication port). It is, for example,
possible to programme
Setup 2
[2], while the active
Setup is set to
Setup 1
[1] in parameter 004
Active
Setup
.
Description of choice:
Factory Setup
[0] contains the factory-set data and can
be used as a source of data if the other Setups are to
be reset to a known status.
Setup 1-4
[1]-[4] are indi-
vidual Setups that can be programmed freely during
operation. If
Active Setup
[5] is selected, the program-
ming Setup will be equal to parameter 004
Active
Setup
.
NOTE:
If data is modified or copied to the active Setup, the
modifications have an immediate effect on the unit's
operation.
006
Setup copying
Value:
No
copying
(NO
COPY)
[0]
Copy to Setup 1 from #
(COPY
TO
SETUP
1)
[1]
Copy to Setup 2 from #
(COPY
TO
SETUP
2)
[2]
Copy to Setup 3 from #
(COPY
TO
SETUP
3)
[3]
Copy to Setup 4 from #
(COPY
TO
SETUP
4)
[4]
Copy to all Setups from # (copy to all)
[5]
Function:
You can copy from the selected active Setup in pa-
rameter 005
Programming setup
to the selected Setup
or Setups in this parameter.
NOTE:
Copying is only possible in Stop (motor stopped in
connection with a stop command).
Description of choice:
Copying begins when the required copying function
has been selected and the [OK]/[CHANGE DATA] key
has been pushed. The display indicates when copy-
ing is in progress.
18
TR1
2800
Series
VFD
Programming
Summary of Contents for VarioTrane TR1 2800 Series
Page 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Page 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Page 4: ...TR1 2800 Series VFD 3...
Page 7: ...6 TR1 2800 Series VFD...
Page 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Page 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Page 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...