223
Warning: Low current, ILOW
Value:
0.0 - par. 224
Warning: High current,
I HIGH
0.0 A
Function:
If the output current falls below the preset limit
ILOW a warning is given.
Parameters 223-228
Warning functions
are out of func-
tion during ramp-up after a start command and after
a stop command or during stop.The warning func-
tions are activated when the output frequency has
reached the resulting reference. The signal outputs
can be programmed to give a warning signal via ter-
minal 46 and via the relay output.
Description of choice:
The lower signal limit of the output current I LOW
must be programmed within the normal working
range of the frequency converter.
224
Warning: High current, IHIGH
Value:
0 - IMAX
IMAX
Function:
If the output current exceeds the preset limit I HIGH a
warning is given.
Parameters 223-228
Warning functions
do not work
during ramp-up after a start command and after stop
command or during stop. The warning functions are
activated when the output frequency has reached the
resulting reference. The signal outputs can be pro-
grammed to give a warning signal via terminal 46 and
via the relay output.
Description of choice:
The output current's upper signal limit I HIGH must
be programmed within the frequency converter's
normal operating range. See drawing at parameter
223
Warning: Low current, I LOW
.
225
Warning: Low frequency, f LOW
Value:
0.0 - par. 226
Warn.: High frequency, f HIGH
0.0 Hz
Function:
If the output frequency falls below the preset limit
f LOW, a warning is given.
Parameters 223-228
Warning functions
are out of func-
tion during ramp-up after a start command and after
stop command or during stop. The warning functions
are activated when the output frequency has reached
the resulting reference. The signal outputs can be
programmed to give a warning signal via terminal 46
and via the relay output.
Description of choice:
The lower signal limit of the output frequency f LOW
must be programmed within the normal operating
range of the frequency converter. See drawing at pa-
rameter 223
Warning: Low current, I LOW .
226
Warning: High frequency f HIGH
Value:
Par. 200
Frequency range
= 0-132 Hz
[0]/[1].par. 225 f LOW - 132 Hz
132.0 Hz
Par. 200
Frequency range
= 0-1000 Hz
[2]/[3].
par. 225 f LOW - 1000 Hz
132.0 Hz
Function:
If the output frequency exceeds the preset limit
f HIGH a warning is given.
Parameters 223-228
Warning functions
do not work
during ramp-up after a start command and after stop
command or during stop. The warning functions are
activated when the output frequency has reached the
resulting reference. The signal outputs can be pro-
grammed to give a warning signal via terminal 46 and
via the relay output.
Description of choice:
The output frequency's upper signal limit f HIGH must
be programmed within the frequency converter's
normal operating range. See drawing at parameter
223
Warning: Low current, I LOW
.
TR1
2800
Series
VFD
37
Programming
Summary of Contents for VarioTrane TR1 2800 Series
Page 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Page 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Page 4: ...TR1 2800 Series VFD 3...
Page 7: ...6 TR1 2800 Series VFD...
Page 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Page 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Page 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...