400
Brake function
Value:
Off
(off)
[0]
Resistor brake
(Resistor)
[1]
AC
brake
(AC
Brake)
[4]
Load sharing (load sharing)
[5]
Factory setting depends on unit type.
Function:
Resistor brake
[1] is selected if the adjustable frequen-
cy drive has an integral brake transistor and brake
resistor is connected to terminals 81, 82. A higher in-
termediate circuit voltage is permitted during braking
(generated operation) when a brake resistor is con-
nected.
AC brake
[4] can be selected to improve braking with-
out using brake resistors. Please note that
AC brake
[4] is not as effective as
Resistor brake
[1].
Description of choice:
Select
Resistor brake
[1] if a brake resistor is connec-
ted.
Select
AC brake
[4] if short-term generated loads oc-
cur. See parameter 144
Gain AC brake
to set the brake.
Select
Load sharing
[5] if this is used.
NOTE:
A change of selection will not become active until the
mains voltage has been disconnected and reconnec-
ted.
405
Reset function
Value:
Manual reset (manual reset)
[0]
Automatic reset x 1
(AUTOMATIC
x
1)
[1]
Automatic reset x 3
(AUTOMATIC
x
3)
[3]
Automatic reset x 10
(AUTOMATIC
x
10)
[10]
Reset at power-up
(RESET
AT
POWER
UP)
[11]
Function:
This parameter makes it possible to select whether
reset and restart after a trip are to be manual or
whether the adjustable frequency drive is to be reset
and restarted automatically. Furthermore, it is possi-
ble to select the number of times a restart is to be
attempted. The time between each attempt is set in
parameter 406
Automatic restart time
.
Description of choice:
If
Manual reset
[0] is selected, reset is to be carried out
via the [STOP/RESET] key, a digital input or serial
communication. If the adjustable frequency drive is
to carry out an automatic reset and restart after a trip,
select data value [1], [3] or [10].
If
Reset at power-up
[11] is selected, the adjustable
frequency drive will carry out a reset if there has been
a fault in connection with the mains failure.
406
Automatic restart time
Value:
0 - 10 sec.
5 sec.
Function:
This parameter allows setting of the time from trip-
ping until the automatic reset function begins. It is
assumed that automatic reset has been selected in
parameter 405
Reset function
.
Description of choice:
Set the required time.
409
Trip delay overcurrent, ILIM
Value:
0 - 60 sec. (61=OFF)
OFF
Function:
When the adjustable frequency drive registers that
the output current has reached the current limit
ILIM (parameter 221
Current limit
) and remains there
for the preset time, it is disconnected. Can be used to
protect the application, like the ETR will protect the
motor if selected.
Description of choice:
Select how long the adjustable frequency drive
should maintain the output current at the current limit
ILIM before it disconnects. At OFF parameter 409
Trip
delay overcurrent, I LIM
is not working, i.e. disconnec-
tion will not take place.
TR1
2800
Series
VFD
47
Special Functions
CAUTION
The motor may start without warning.
Programming
Summary of Contents for VarioTrane TR1 2800 Series
Page 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Page 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Page 4: ...TR1 2800 Series VFD 3...
Page 7: ...6 TR1 2800 Series VFD...
Page 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Page 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Page 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...