According to international stand-
ards
Type 2803
2805
2807
2811
2815
2822
2840
Output
current
IINV. [A]
2.2
3.2
4.2
6.0
6.8
9.6
16
(3 x 200-240V)
IMAX (60s) [A]
3.5
5.1
6.7
9.6
10.8
15.3
25.6
Output power (230
V)
SINV. [KVA]
0.9
1.3
1.7
2.4
2.7
3.8
6.4
Typical shaft output
PM,N [kW] 0.37
0.55
0.75
1.1
1.5
2.2
3.7
Typical shaft output
PM,N [HP]
0.5
0.75
1.0
1.5
2.0
3.0
5.0
Max. cable cross sec-
tion, motor
[mm2 /AWG] 1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Input
current
IL,N [A]
5.9
8.3
10.6
14.5
15.2
-
-
(1 x 220-240 V)
IL,MAX (60s) [A]
9.4
13.3
16.7
23.2
24.3
-
-
Input
current
IL,N [A]
2.9
4.0
5.1
7.0
7.6
8.8
14.7
(3 x 200-240 V)
IL,MAX (60s) [A]
4.6
6.4
8.2
11.2
12.2
14.1
23.5
Max. cable cross sec-
tion, power
[mm2 /AWG] 1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Max. pre-fuses
IEC/UL2) [A] 20/20
20/20
20/20
20/20
20/20
20/20
25/25
Efficiency3)
[%]
95
95
95
95
95
95
95
Power loss at 100%
load
[W]
24
35
48
69
94
125
231
Weight
[kg] 2.0
2.0
2.0
3.7
2.0
2.0
6.0
Enclosure4
type IP
20
IP
20
IP
20
IP
20
IP
20
IP
20
IP
20
1. American Wire Gauge. Max. cable cross section is the largest cable cross section that can be attached to the
terminals. Always observe national and local regulations.
2. Type gG pre-fuses must be used for installation according to IEC rules. If you want to maintain UL/cUL you
must use pre-fuses of the type Bussmann KTN-R 200 V, KTS-R 500 V or Ferraz Shawmut, type ATMR (max. 30A).
The fuses must be placed for protection in a circuit that is capable of supplying a maximum of 100,000 amps
RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured motor cable with a rated load and rated frequency.
4. IP20 is standard for TR1 2805-2875, whereas NEMA 1 is an option.
TR1
2800
Series
VFD
121
Technical Data, Mains Supply 1 x 220 - 240 V/3 x 200 - 240 V
All about TR1 2800 Series VFD
Summary of Contents for VarioTrane TR1 2800 Series
Page 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Page 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Page 4: ...TR1 2800 Series VFD 3...
Page 7: ...6 TR1 2800 Series VFD...
Page 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Page 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Page 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...