Table 18.
Touchscreen interface active alarm states (continued)
Alarm
Application
Type
Action
BMS OFFLINE
Primary
Auto Reset
Warning
cpCOe UI1 SENSOR FAILURE
Primary
Auto Reset
Switches Primary module and secondary modules in
Stand-alone Mode *
cpCOe UI2 SENSOR FAILURE
Primary
Auto Reset
Switches Primary module and secondary modules in
Stand-alone Mode *
cpCOe UI3 SENSOR FAILURE
Primary
Auto Reset
Switches Primary module and secondary modules in
Stand-alone Mode *
cpCOe UI4 SENSOR FAILURE
Primary
Auto Reset
Switches Primary module and secondary modules in
Stand-alone Mode *
cpCOe UI5 SENSOR FAILURE
Primary
Auto Reset
Warning
cpCOe UI6 SENSOR FAILURE
Primary
Auto Reset
Warning
cpCOe UI7 SENSOR FAILURE
Primary
Auto Reset
Switches to Internal Cooling set point if ‘External' is
selected
cpCOe UI8 SENSOR FAILURE
Primary
Auto Reset
Switches to Internal Cooling set point if ‘External' is
selected
cpCOe OFFLINE ALARM
Primary
Auto Reset
Switches Primary module and secondary modules in
stand-alone mode
cpCOe WRONG CONFIG Alarm
Primary
Auto Reset
Warning
UI1 SENSOR FAILURE
Primary / Secondary
Auto Reset
Shuts down local cooling control ***
UI2 SENSOR FAILURE
Primary / Secondary
Auto Reset
Shuts down local cooling control ***
UI3 SENSOR FAILURE
Primary / Secondary
Auto Reset
Shuts down local heating control ***
UI4 SENSOR FAILURE
Primary / Secondary
Auto Reset
Shuts down module if ‘LP Alarm Mode = Sensor’
UI5 SENSOR FAILURE
Primary / Secondary
Auto Reset
Shuts down module
UI6 SENSOR FAILURE
Primary / Secondary
Auto Reset
Shuts down local heating control ****
UI7 SENSOR FAILURE
Primary / Secondary
Auto Reset
Warning
UI8 SENSOR FAILURE
Primary / Secondary
Auto Reset
Locks out module if it is running in heating mode
UI9 SENSOR FAILURE
Primary / Secondary
Auto Reset
Warning
UI10 SENSOR FAILURE
Primary / Secondary
Auto Reset
Warning
UI12 SENSOR FAILURE
Primary / Secondary
Auto Reset
Warning
COMPRESSOR 1 WARNING
Primary / Secondary
Auto Reset
Warning
COMPRESSOR 1 FAILURE
Primary / Secondary
Auto Reset
Shuts down compressor 1
COMPRESSOR 1 FAILURE
Primary / Secondary
Auto Reset
Shuts down compressor 1 *****
COMPRESSOR 1 CORESENSE FAILURE
Primary / Secondary
Auto Reset
Shuts down compressor 1
COMP 1 CORESENSE COMMUNICATION
LOST
Primary / Secondary
Auto Reset
Shuts down compressor 1
COMPRESSOR 2 WARNING
Primary / Secondary
Auto Reset
Warning
COMPRESSOR 2 FAILURE
Primary / Secondary
Auto Reset
Shuts down compressor 2
COMPRESSOR 2 FAILURE
Primary / Secondary
Auto Reset
Shuts down compressor 2*****
COMPRESSOR 2 CORESENSE FAILURE
Primary / Secondary
Auto Reset
Shuts down compressor 2
Comp 2 CORESENSE COMMUNICATION
LOST
Primary / Secondary
Auto Reset
Shuts down compressor 2
EVD OFFLINE
Primary / Secondary
Auto Reset
Warning