12
ARTC-SVX005B-EN
Table 2. Chiller/Heater bank dimensions for all configurations (continued)
# OF
MODULES
DIM
1
2
3
4
5
6
7
8
9
10
INCH
INCH
INCH
INCH
INCH
INCH
INCH
INCH
INCH
INCH
60 Ton
PolyTherm
A
42
84
126
168
210
252
294
336
378
420
B
84
84
84
84
84
84
84
84
84
84
C
17 1/2
17 1/2
17 1/2
17 1/2
17 1/2
17 1/2
17 1/2
17 1/2
17 1/2
17 1/2
D
75
75
75
75
75
75
75
75
75
75
LBS
2,040
4,080
6,120
8,160
10,200
12,240
14,280
16,320
18,360
20,400
Chiller/Heater Clearances
The National Electric Code or local, state, and regional
building codes may require greater clearance for the
modular chiller/heater than the figures listed in this
publication. Always consult local regulatory agencies
to ensure additional clearances are not required by
building codes.
Minimum Clearances
The unit must maintain a minimum of 36-inch
clearance on all sides. See
N
No
otte
e:: These clearances are general recommendations.
Each installation has specific considerations.
Contact Trane for definitive guidance and
approval on a job-by-job basis.
Mounting Rails
The chiller/heater must be positioned on a firm, level
surface. All modules should be installed onto structural
steel rails. The rails must be level, be a minimum of 4-
inch wide (preferably 6-inch wide), and seated on
springs/pads.
Custom modules may have different requirements.
Consult submittal drawings to confirm dimensions.
After setting and lubricating the mounting rails, begin
installing the modules. All of the modules arrive with
labels on the electrical and control panel. Review the
installation drawings to determine which is the first,
primary module. Typically the primary module also has
the main power distribution panel attached to it.
For vibration isolation, spring isolators or rubber-in-
shear isolator pads must be installed under the
structural steel mounting rails.
N
NO
OT
TIIC
CE
E
C
Co
on
nn
ne
eccttiio
on
n L
Le
ea
akkss!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w iin
nssttrru
uccttiio
on
nss b
be
ello
ow
w cco
ou
ulld
d rre
essu
ulltt iin
n
d
da
am
ma
ag
ge
e tto
o tth
he
e cco
oiill h
he
ea
ad
de
err a
an
nd
d cca
au
usse
e cco
on
nn
ne
eccttiio
on
n
lle
ea
akkss..
U
Usse
e a
a b
ba
acckku
up
p w
wrre
en
ncch
h w
wh
he
en
n a
atttta
acch
hiin
ng
g p
piip
piin
ng
g tto
o
cco
oiillss w
wiitth
h cco
op
pp
pe
err h
he
ea
ad
de
errss.. D
Do
o n
no
ott u
usse
e b
brra
assss
cco
on
nn
ne
ecctto
orrss b
be
ecca
au
usse
e tth
he
ey
y d
diisstto
orrtt e
ea
assiilly
y..
Figure 3. Recommended chiller/heater clearances