116
CLCH-SVX07C-EN
Start-Up
Field-obtained factors can provide maximum accuracy. To obtain the factor in the field, measure
the differential pressure output from the transmitter while measuring the airflow through the
system. Once these two values have been measured, simply solve for K using the following
equation:
Fan Size (inches)/Type
Fan Class
Fan Name
K-Factor
32 FC
Class I
32 FA
20400.0
32 FC
Class II
32 FB
20150.0
36 FC
Class I
36 FA
28049.9
36 FC
Class II
36 FB
27549.0
40 FC
Class I
40 FA
39236.4
40 FC
Class II
40 FB
38067.7
10 BC belt-drive plenum
Class I or II
10 PA or 10 PB
563.0
11 BC belt-drive plenum
Class I or II
11PA or 11 PB
703.0
12 AF belt-drive plenum
Class I or II
12PA or 12 PB
1168.7
14 AF belt-drive plenum
Class I or II
14PA or 14 PB
1536.1
16 AF belt-drive plenum
Class I or II
16PA or 16 PB
1870.
18 AF belt-drive plenum
Class I or II
18PA or 18 PB
2270.7
20 AF belt-drive plenum
Class I or II
20PA or 20 PB
2905.2
22 AF belt-drive plenum
Class I or II
22PA or 22 PB
3673.2
25 AF belt-drive plenum
Class I or II
25PA or 25 PB
4608.2
28 AF belt-drive plenum
Class I or II
28 PA or 28 PB
6277.8
32 AF belt-drive plenum
Class I or II
32 PA or 32 PB
7847.3
36 AF belt-drive plenum
Class I or II
36 PA or 36 PB
10017.8
40 AF belt-drive plenum
Class I or II
40 PA or 40 PB
13023.1
44 AF belt-drive plenum
Class I or II
44 PA or 44 PB
14692.8
49 AF belt-drive plenum
Class I or II
49 PA or 49 PB
18299.2
55 AF belt-drive plenum
Class I or II
55 PA or 55 PB
23901.0
63 AF belt-drive plenum
Class I or II
63 PA or 63 PB
31135.0
10.5 AF direct-drive plenum
Class II
10 NF or 10 NW
630
13.5 AF direct-drive plenum
Class II
13 NR or 13 NF
952
15 AF direct-drive plenum
Class II
15 NR or 15 NF
1139
18 AF direct-drive plenum
Class II
18 NR or 18 NF
1673
20 AF direct-drive plenum
Class II
20 NR or 20 NF
1942
22 AF direct-drive plenum
Class II
22 NR, 22 NF, or 22 NW
2454
24 AF direct-drive plenum
Class II
24 NR, 24 NF, or 24 NW
3010
27 AF direct-drive plenum
Class II
27 NR or 27 NF
3701
30 AF direct-drive plenum
Class II
30 NR or 30 NF
4620
22 AF stacked direct-drive plenum
Class II
22 SF or 22 SW
2849
24.5 AF stacked direct-drive plenum
Class II
24 SF or 24 SW
4765
Note:
(1) to be used for fan rpm < 700 or cfm < 25,500. (2) to be used for fan rpm > 700 or cfm > 25,500
K = ACFM/SQRT(DP)
Where:
K = Field-provided constant factor.
ACFM = Actual airflow (ft
3
/min.) being measured at the air density being measured.
DP = Differential pressure (inches w.g.) being measured by the transmitter.
Table 32. Constant K Factors
Summary of Contents for AM4A0A18S11SA Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 4: ......
Page 100: ...96 CLCH SVX07C EN Installation Electrical Figure 84 Typical VFD wiring schematic ...
Page 101: ...CLCH SVX07C EN 97 Installation Electrical Figure 85 Typical starter wiring schematic ...
Page 135: ...CLCH SVX07C EN 131 Notes ...
Page 146: ...10 1 2 STEP 8 Lift the Coil section up and away from the Blower section Set aside ...
Page 178: ......
Page 188: ...2 ...
Page 189: ...3 ...
Page 190: ...4 ...
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 250: ......
Page 251: ......