CLCH-SVX07C-EN
113
Start-Up
Table 31.
Back or top inlet low-flow Traq dampers - air-mixing and indoor economizer sections - VCM voltage versus airflow at sea level
Unit
Size
Part
Number
Traq
Damper
Size (in)
Damper
Type
Quantity
Peak Velocity
(fpm)
Total Area
(ft
2
)
CFM @ 10VDC
Peak Velocity
L/s @ 10VDC
Peak Velocity
4
50182901
13
Min. Outside Air
1
2475
0.92
2279
1076
Economizing
1
0.92
2279
1076
6
50182901
13
Min. Outside Air
1
2475
0.92
2279
1076
Economizing
1
0.92
2279
1076
8
50182901
13
Min. Outside Air
1
2475
0.92
2279
1076
Economizing
2
1.84
4554
2149
10
50182901
13
Min. Outside Air
1
2475
0.92
2279
1076
Economizing
2
1.84
4554
2149
12
50182902
16
Min. Outside Air
1
2475
1.40
3455
1630
Economizing
2
2.79
6910
3261
14
50182902
16
Min. Outside Air
1
2475
1.40
3455
1630
Economizing
2
2.79
6910
3261
17
50182902
16
Min. Outside Air
1
2475
1.40
3455
1630
Economizing
2
2.79
6910
3261
21
50182924
20
Min. Outside Air
1
2600
2.18
5671
2676
Economizing
2
4.36
11341
5352
25
50182924
20
Min. Outside Air
1
2600
2.18
5671
2676
Economizing
2
4.36
11341
5352
30
50182903
24
Min. Outside Air
1
2600
3.14
8164
3853
Economizing
2
6.28
16328
7705
35
50182903
24
Min. Outside Air
1
2600
3.14
8164
3853
Economizing
2
6.28
16328
7705
40
50182903
24
Min. Outside Air
1
2600
3.14
8164
3853
Economizing
2
6.28
16328
7705
50
50182904
28
Min. Outside Air
1
2600
4.27
11112
5244
Economizing
2
8.55
22224
10488
57
50182904
28
Min. Outside Air
1
2600
4.27
11112
5244
Economizing
2
8.55
22224
10488
66
50182904
28
Min. Outside Air
1
2600
4.27
11112
5244
Economizing
3
12.82
33336
15731
80
50182904
28
Min. Outside Air
1
2600
4.27
11112
5244
Economizing
4
17.10
44448
20975
100
50182904
28
Min. Outside Air
1
2600
4.27
11112
5244
Economizing
5
8.55
22224
10488
120
50182904
28
Min. Outside Air
1
2600
4.27
11112
5244
Economizing
5
21.37
55561
26219
Trane utilizes AMCA certification for airflow measuring stations. Trane certifies that the Traq damper
herein is licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed
in accordance with AMCA Publication 611 and comply with the requirements of the AMCA Certified
Ratings Program.
The certification program provides the engineer and owner assurance that manufacturer-published
performance ratings for airflow measurement stations are accurate and repeatable. Trane Traq dampers
are certified with the integral ventilation control module which converts differential pressure to an
electronic signal for control.
Refer to Performance Climate Changer Air Handler catalog CLCH-PRC015-EN for Traq damper testing and
rating information.
Summary of Contents for AM4A0A18S11SA Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 4: ......
Page 100: ...96 CLCH SVX07C EN Installation Electrical Figure 84 Typical VFD wiring schematic ...
Page 101: ...CLCH SVX07C EN 97 Installation Electrical Figure 85 Typical starter wiring schematic ...
Page 135: ...CLCH SVX07C EN 131 Notes ...
Page 146: ...10 1 2 STEP 8 Lift the Coil section up and away from the Blower section Set aside ...
Page 178: ......
Page 188: ...2 ...
Page 189: ...3 ...
Page 190: ...4 ...
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 250: ......
Page 251: ......