105
Start-Up
Calculate Motor Voltage Imbalance
After startup, measure the motor voltage and amperage on all phases to ensure proper operation.
The readings should fall within the range given on the motor nameplate. The maximum allowable
voltage imbalance is 2 percent.
Voltage imbalance is defined as 100 times the sum of the deviation of the three voltages from the
average, divided by twice the average voltage. For example, if the three measured voltages are 221,
230 and 227, the average voltage would be 226 volts. The percent of voltage imbalance is then
calculated.
Voltage imbalance =
where:
A = (226-221) + (230-226) + (227-226)
Voltage imbalance = 2.2% (not acceptable)
In the example, 2.2 percent imbalance is not acceptable and the power company should be notified
to correct it.
100A
2
AvgVoltage
×
--------------------------------------------------
Summary of Contents for AM4A0A18S11SA Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 4: ......
Page 100: ...96 CLCH SVX07C EN Installation Electrical Figure 84 Typical VFD wiring schematic ...
Page 101: ...CLCH SVX07C EN 97 Installation Electrical Figure 85 Typical starter wiring schematic ...
Page 135: ...CLCH SVX07C EN 131 Notes ...
Page 146: ...10 1 2 STEP 8 Lift the Coil section up and away from the Blower section Set aside ...
Page 178: ......
Page 188: ...2 ...
Page 189: ...3 ...
Page 190: ...4 ...
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 250: ......
Page 251: ......