98
CLCH-SVX07C-EN
Installation - Electrical
Note:
Properly seal all penetrations in unit casing. Failure to seal penetrations from inner panel
to outer panel could result in unconditioned air entering the unit.
All units with starters or variable-frequency drives (VFDs) that have direct-digital controllers (DDCs)
are provided with line voltage to 24 Vac power transformers (see
Figure 86
). All units with factory-
mounted controllers, and no starters or VFDs, are provided with 120 Vac to 24 Vac control
transformers (see
Figure 87
).
Figure 88
shows a typical VFD power box.
Note:
The valve jack is typically located at the air-leaving side of the coil connection inside the
casing panel.
To provide field-wiring to units with DDC controls:
•
If VFD or starter is not factory-mounted, provide 120 Vac power to a transformer in the controller
enclosure. A separate circuit is recommended (see
Figure 87
).
•
Install outside-air sensor and space sensor, if ordered.
•
For valve junction box mounting and wiring detail, see
Figure 89
.
Figure 86. Transformer plate
Figure 87. 120 to 24 Vac Control
Transformer
Figure 88. Variable-frequency drive
(VFD)
Summary of Contents for AM4A0A18S11SA Series
Page 1: ......
Page 2: ......
Page 3: ......
Page 4: ......
Page 100: ...96 CLCH SVX07C EN Installation Electrical Figure 84 Typical VFD wiring schematic ...
Page 101: ...CLCH SVX07C EN 97 Installation Electrical Figure 85 Typical starter wiring schematic ...
Page 135: ...CLCH SVX07C EN 131 Notes ...
Page 146: ...10 1 2 STEP 8 Lift the Coil section up and away from the Blower section Set aside ...
Page 178: ......
Page 188: ...2 ...
Page 189: ...3 ...
Page 190: ...4 ...
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 250: ......
Page 251: ......