tousek
/ EN_ST-80-M-S_05 / 25. 03. 2020
- 17 -
Peripherals
Connections and adjustments
Magnetic clamp
(terminals
M/S
74 (-) / 75 (+))
M/S
Peripherals
OFF
0,1–1s adjustable:
before boom opening the magnetic clamp is being turned off - the boom opens only after the
adjusted time. In closed position the magnetic clamp is automatically switched on.
Magnet for boom fixing
M/S
• The barrier can be equipped with a magnet
24Vd.c., 5W max.
for fixing the boom in closed position. This is connected
via a series resistor
(R magnet)
to the controller ST 80 Master/Slave.
Connection of magnet
•
ATTENTION: turn off power supply!
• The magnet has to be connected to the control via a
protective resistor.
This protective resistor is designed for the tousek
adhesive magnets GD 70.
• Slide the connecting cable of the magnet, as shown
in picture, ldet, into the opening of the resistor and fix
it with Crimp wrench.
• Connecting cables and series resistor have to be
connected
,
as shown, with
terminals 74(–) / 75(+)
of the control board.
Pay attention to polarity.
70
71
74
75
9/1
9/2
9/3
9/4
78
79
R
Magnet
fix
24V
– +
Signal contacts
M
Peripherals
Status display 1:
with the two potential free signal contacts
K1
and
K2
the adjustments of the barrier can be evaluated.
Status display 2:
with the two potential free signal contacts
K1
and
K2
the adjustments as well as the movement
direction of the barrier can be evaluated.
Status display module
(optional)
M
•
turn off power supply before installing the
additional module!
• The module „
Gate status display“
has to be plugged to the
according slot/plug
(ZM)
of control board.
• Additionally the corresponding value has to be selected in menu
point „signal contacts“
Additional module Gate status display
• with potential free signal contacts K1 (Kl. 90/91) and K2 (Kl. 92/93)
the gate staturs can be evaluated in two ways.
• Contact load:
24Va.c./d.c., max. 10W
function
K1
K2
Barrier status display
1
Barrier in CLOSE-Position
1
0
Barrier in OPEN-Position
0
1
2
Barrier in CLOSE-Position
1
1
Barrier opens or has been stopped in the process
1
0
Barrier closes or has been stopped in the process
0
1
Barrier in OPEN-Position
0
0
Signal contact: 0 = open, 1= closed
90 91 92 93
signal contacts
K1
K2
ZM