Danger
•
Before connection works or taking off the housing cover the power supply has to be turned off !
•
Please check the adjustments to be in compliance with the valid safety regulations and standards that have to
be strictly followed !
see also safety instructions on page 5 !
Motor
Connections and adjustments ST 80(V)
max. force
100% (factory setting)
M/S
Motor
50–100% adjustable [increment 5]:
determines the max. possible motor force.
ARS response time
0,5s (factory setting)
M/S
Motor
0,15–0,95s closing speed adjustable [increment 0,05]:
determines, in which time the AR-System responds. The
lower the value, the more sensitive the sensor will react.
Speed OPEN
90% for ST80 /
100% for ST80V (factory setting)
M/S
Motor
55–100% adjustable [increment 5]:
determines the speed of motor during opening.
At barriers with 6m boom length the setting for speed OPEN must not be more than 90% (= factory
setting of ST 80)
!
Speed CLOSE
90% for ST80 /
100% for ST80V (factory setting)
M/S
Motor
55–100% adjustable [increment 5]:
determines the speed of motor during closing.
At barriers with 6m boom length the setting for speed CLOSE must not be more than 90% (= factory
setting of ST 80)
!
Soft runtime
1,5s for ST80 /
1s for ST80V (factory setting)
M/S
Motor
0–5s adjustable [increment 0,1]:
determines the time of softstop.
Operating logic
Connections and adjustments
Impulse logic
M
Operating logic
without pause time extension:
a command in automatic mode during pause time does not lead to a pause time
extension. The impulse is being ignored.
with pause time extension:
a command in automatic mode during pause time restarts pause time.
Motor partial opening
M
Operating logic
Master:
partial opening by Master barrier.
Slave:
partial opening by Slave barrier.
G
Operating mode
M
Operating logic
Impulse mode:
Impulse through impulse switch/button or CLOSE-button to start closing of barrier.
Automatic mode, pause time 1-255s adjustable [increment 1]:
barrier closes automatically after the adjusted
pause time.
Exception: If the system is in the partial open position (i.e., only the partial opening barrier boom is open) and a com-
mand by an impulse emitter switch (or radio transmitter) for a full opening is given (both barrier booms are open), then
after the pause time has elapsed, the system returns to the partial open position (i.e., only the barrier responsible for
the partial opening remains open, the other closes).
Pause time logic
M
Operating logic
no influence
permanent open in automatic mode:
If „always open in automatic mode“ and „pause time“ are simultaneaus activated
the automatic mode can be deactivated. An impulse in complete open position causes a switch into „impulse mode“
but only for hte current cycle. So the gate stays in OPEN position. The next impulse closes the gate an the control unit
switched to „automaitc mode“ again. This function allows that the entrance of a company site stays open during the day
(first impulse in complete open position). The gate can be closed with the second impulse e.g. in the evening (second
impulse - for closing the gate and switching to the „automatic mode“). The control unit switches to the „automatic mode“
again (automatic opening and closing of the gate).
Note:
An impulse through the pedestrian button in the complete open position doesn´t start the „always open“ function.
This action causes a movement in CLOSE direction and the gate stopps at pedestrian OPEN position.
If the gate is in partial open position and „permanent open in automatic mode“ is selected, so it is possible to adjust
permanent partial open for this cycle by giving an impulse via pedestrian button. Permanent partial open can be finished
analogous to the above described method.