- 10 - 

tousek

  /  EN_ST-80-M-S_05  /  25. 03. 2020

 Important

•  As impulse-, pedestrian-, close- buttons pushbuttons or key switches as well as external command devices with  

potential free make contacts can be used.

•  As stop switch a break contact has to be used!!

The stop input has no emergency stop function! - In order to ensure the emergency stop function, 

provide the supply line with an all-pole disconnecting emergency stop switch, that locks after actuation!

•  A general status display of all inputs can be found in the menu DIAGNOSIS / STATUS DISPLAY

Buttons/switches

 

Connections and adjustments

 

G

  Impulse switch  

(terminals 

M

 30/32)  

M

 

Buttons/switches

 

OPEN / CLOSE / OPEN impulse repetition: 

After a command of the impulse switch the motor starts an open or close 

movement. If the impulse switch is pressed again during this movement, the motor reverses.(an impulse during open-

ing movement is ignored).

 

  In this operation mode it is not possible to stop the motor with the impulse switch – it always 

travels until reaching an end position. (Opened or closed position).

•  for the function OPEN/CLOSE/OPEN we strongly suggest the installation of a photocell!

 

 

OPEN: 

Only open commands are accepted of the impulse switch. Closing the barrier with the impulse switch is not 

possible.

 

DEADMAN: 

The motor opens as long as the impulse switch is pressed – closing the barrier with the impulse switch is 

not possible. As soon as the switch is released, the barrier boom stops. If deadman mode is selected, the radio receiver 

is set out of order for safety reasons.

 

•  If the impulse switch is set to DEAD MAN operation, then the partial opening switch works the same way. 

With the impulse- or the partial opening switch the barrier is opened, with the CLOSE-button it is closed.

•  IMPORTANT: Do not put into operation in dead man mode.  

Select only after putting into operation (

 

page 21), if desired.

4.  Connections and adjustments 

Barrier control ST 80, ST 80V / Master-Slave

 

Barrier door contact    

(terminals 30/54)                                   

 

M/S

• 

When opening the barrier door, a safety contatct is released which  stops any 

boom movement. The last indications on the display remain unchanged.

• 

If the door is closed again, the open position of barrier boom is being newly 

learned/programmed.

30

54

barrier door contact

The different menu points, that can be selected in the Master control board (= 

M

) or in the Master and in the 

Slave control board (= 

M/S

) are indicated as follows:

 =  selectable setting (or possible value assignment)     

 = factory settings     

 = status display

G

 shows the menu points which are in the “ BASIC SETTINGS”

Furthermore connection notes and other instructions are indicated as follows 

M

 = regards the Master control board  

M/S

 = regards the Master ans Slave control board

 Danger

• 

Before connection works or taking off the housing cover the power supply has to be turned off !

    

 

• 

When connecting control boards, impulse emitters, safety devices and motors as well as when adjusting the 

power of the operators, it is essential to comply with the applicable safety regulations and standards! 

 

 also follow safety instructions 5 !

Summary of Contents for ST 80

Page 1: ...Installation and connection manual Barrier control ST 80 ST 80V Master Slave combination for double barrier...

Page 2: ...he manual replaces all earlier publications of the same Index General warning and safety details 3 1 Notes general characteristics control board layout technical data 4 5 2 Terminal assignment 5 7 3 P...

Page 3: ...They may be hazardous to children and therefore have to be stored out of children s reach The product is not suitable for installation in explosion hazardous areas The product may only be used in acc...

Page 4: ...mmingwithilluminatedLCdisplayinenglischlanguage Three operating modes impulse automatic deadman Automatic closing with adjustable pause time Runtime of operator is being automatically determined Separ...

Page 5: ...plosion hazardousareas An all pole disconnecting mains switch with a contact opening gap of min 3 mm has to be foreseen The barrier facility has to be secured according to the valid safety regulations...

Page 6: ...ns switch with a contact opening gap of min 3 mm has to be foreseen The barrier facility has to be secured according to the valid safety regulations IMPORTANT The control lines sensor buttons radio ph...

Page 7: ...l with slave control the terminals 88 and 89 of system plugs of each control have to be connected with each other see picture below Important max cable length between the barrier housings is 25m Cable...

Page 8: ...the shown value of a parameter is given When pressing the button you return to the superior menu point Possibly changed adjustments of a parameter are rejected with this button the former values will...

Page 9: ...with pause time extension M motor partial opening Master Slave M G operating mode impulse mode automatic 1 255s increment 1 M pause time logic no influence constant open in automatic mode M forced clo...

Page 10: ...r boom stops If deadman mode is selected the radio receiver is set out of order for safety reasons If the impulse switch is set to DEAD MAN operation then the partial opening switch works the same way...

Page 11: ...Note if the function open under menu point is selected and if the impulse switch is set to DEADMAN then the opening of the boom is omitted when driving over the I loop 9 1 9 2 9 3 9 4 I loop 1 I loop...

Page 12: ...two pairs of photocells please do not install both photocell transmitters receivers on the same side to eleminate interference between both Exception photocells with SYNC function allow the installati...

Page 13: ...J 2 photocells Tousek LS 41 LS 180 as safety device with SYNC function activated N O COM N C J J N O COM N C transmitter 1 receiver 1 transmitter 2 receiver 2 41 42 43 44 45 46 SYNC J Important As the...

Page 14: ...sing command has to be actuated Stop during closing then close an interruption of the photocell beam or induction loop during closing makes the motor stop as long as the photocell loop stays interrupt...

Page 15: ...barrier G Operating mode M Operating logic Impulse mode Impulse through impulse switch button or CLOSE button to start closing of barrier Automatic mode pause time 1 255s adjustable increment 1 barri...

Page 16: ...rd the setting is made via Master control Prewarning OPEN signal lamp terminals M S 10 11 M Light lamps turned off 1 30s adjustable Before each opening movement the signal lamp flashing light is activ...

Page 17: ...ay attention to polarity 70 71 74 75 9 1 9 2 9 3 9 4 78 79 R Magnet fix 24V Signal contacts M Peripherals Status display 1 with the two potential free signal contacts K1 and K2 the adjustments of the...

Page 18: ...are newly set after an impulse Software version control function M S Reset Diagnosis shows the software version on display Serial number control function M S Reset Diagnosis shows the serial number o...

Page 19: ...can be made easily with the rotary switches D1 for channel 1 and D2 for channel 2 as well a s the DIP switches DIP see corresponding manual Factory settings DIP1 DIP8 OFF D1 and D2 4 DIP DIP switch RE...

Page 20: ...eiver please see manual for radio receiver Turn off power supply Open cover of control unit Receiver board E RS433 868 STN1 1 channel or RS433 868 STN2 2 channel into the connection slot FE as shown i...

Page 21: ...aster control Exit using ESC button system tests of the master control are carried out If an error occurs you get into the BASIC SETTINGS again by pressing the ENTER button After the successfull syste...

Page 22: ...utton for 5s from any position in menu Master control M Putting into operation BASIC SETTING of Master control For setting the most important adjustments for initial operation of motor Can be selected...

Page 23: ...gered This would lead to an interruption of the programming process Operation mode Operation mode impulse mode Operation mode aut close 5s Operation mode aut close 10s System test Photocell System tes...

Page 24: ...status dispaly for help Display Low Voltage undervoltage check supply line Display search Master communication problem check connection transmission Display search Slave communication problem check co...

Page 25: ...05 25 03 2020 25 240 195 depth 105 9 Dimensioned drawing of box IP54 Barrier control ST 80 ST 80V Master Slave dimensions in mm We reserve the right to change dimensions and technical specifications w...

Page 26: ...used All shear crush and pinch points of the door system must be protected absolutely In this context we refer to the Machinery Directive and safety regulations and EU standards in their country or as...

Page 27: ......

Page 28: ...Gliwicka 67 Tel 48 32 738 53 65 Fax 48 32 738 53 66 info tousek pl Tousek s r o Czech Republic CZ 252 61 Jene u Prahy Pr myslov 499 Tel 420 777 751 730 info tousek cz We reserve the right to change di...

Reviews: