ISD channel 1
(I-loop 1: terminals 9/1 and 9/2)
M
Buttons / switches
open:
when driving over I-loop 1 the Master and Slave barrier will open.
Safety:
when driving over I-loop 1 the chosen setting under „LS/ISD-function“
(
page 14)
is effected.
Attendance:
through a potential free closing-contact (terminals 78/79) the driving over the I-loop 1 can be evaluated.
Open Master:
when driving over I-loop 1 only the Master barrier will open.
ISD channel 2
(I-loop 2: terminals 9/3 and 9/4)
M
Buttons / switches
open:
when driving over I-loop 2 the Master and Slave barrier will open.
Safety:
when driving over I-loop 2 the chosen setting under „LS/ISD-function“
(
page 14)
is effected
Attendance:
through a potential free closing-contact (terminals 78/79) the driving over the I-loop 2 can be evaluated.
Open Master:
when driving over I-loop 2 only the Master barrier will open.
Induction loops
M
•
With the optional available induction loop detector
(see page17)
the use of induction
loops is made possible.
Connection I-loop 1: Kl. 9/1, 9/2, I-loop 2: Kl. 9/3, 9/4
• The function of I-loops has to be selected under
„ISD channel 1“
and
„ISD channel 2“
:
Note:
if the function
„open“
under menu point is selected and if the impulse switch is set to
„DEADMAN“
, then the opening of the boom is omitted when driving over the I-loop !
9/1
9/2
9/3
9/4
I-loop 1
I-loop 2
CLOSE-button
(terminals
M
30/33)
Buttons/ switches
• A command with the CLOSE-switch engages closing of barrier. In deadman mode the barrier closes as long as the
CLOSE-switch is pressed/switched.
As soon as switch is released the barrier movement stops.
Partial opening button
(terminals
M
30/34)
Buttons/ switches
• same function as impulse switch.
This button has the function of partial opening, i.e. only the barrier defined for the partial opening is opened
(
menu item „operating mode“ / „motor partial opening“).
A partial opening impulse in the open position causes the system to change into partial open position (i.e. only the
barrier responsible for the partial opening remains open, the other closes).
STOP-switch
(terminalsi
M/S
31/37)
Buttons / switches
• when pressing the stop switch the gate stops in any desired position.
As stop switch a break contact has to be used.
If no stop switch is connected, terminals 31/37 have to be wire-bridged.
31
37
M/S
The stop input has no emergency stop function! - In order to ensure the emergency stop function, provide
the supply line with an all-pole disconnecting emergency stop switch, that locks after actuation!