1-11
XRC-195 Board Specifications, Cont.
Table 1–1 XRC Board Component Descriptions
ID Number
Description
ID Number
Description
1
SRAM (Lithium backed)
15
A-PI/DI/DO Connectors
2
Flash Program Memory
16
B- PI/DI/DO Connectors
3
Prom Loader/Utilities Memory
17
Remote Comm 1: Connectors
4
Factory Maintenance Interface
18
Remote Comm 2: Connectors
5
Keypad Connector
19
Remote Comm 2: RS-485 Term. Jumper
6
Security Switch
20
Remote Comm 2: Module Plug-in
7
Lithium Battery
21
Remote Comm 1: RS-485 Term. Jumper
8
Battery Cover
22
Remote Comm 1: Module Plug-in
9
Battery Mounting Bracket
23
External Charger Connector
10
Memory Backup Enable/Disable
24
Battery Connection
11
Analog Input Connectors
25
I/O Module Interface
12
Analog Input Selection Jumper
26
LCD Display Interface
13
Aux. Power Output Connectors
27
PCCU Interface
14
DeBounce Enable/Disable
28
SDRIVE: 32K E2Prom
29
Contrast Potentiometer
XSeries On-board Input/Output
Totalflow's XRC features the base I/O listed below:
•
5 User A/I's
•
4 User D/O's
•
4 User D/I’s (2 may be used as High Speed P/I’s (D/I 1 and D/I 2))
•
2 RS232 or 485 Comm Ports
•
1 Dedicated Local Communication Port
•
Interface for TFIO Modules
The Main Electronic Board (XRC-195 Board) is an enhanced replacement for previous
versions of the RTU Main Electronic Board. In the next few pages, you will see the
specifications for Digital/Pulse Input, Digital Output and Analog Input. To see a complete
overview of the XRC-195 Board, see Figure 1–5.
Comm. Ports
You have the ability to program up to two on-board communication ports
on the XRC-195 Board. Normally COMM 0 is the local port required for
reading the XRC with a laptop computer running PCCU32. COMM 1 and
COMM 2 can be configured for any combination of RS 232 or RS 485.
See Figure 1–5 for On-Board Communication Ports.
Summary of Contents for XRC6490
Page 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Page 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Page 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Page 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Page 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Page 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...