A-71
8.
PI Status Flags: 1=low limit exceeded; 2=high limit exceeded; 8=zero flow.
9.
Ext Status Flags: 1=low limit exceeded; 2=high limit exceeded; 8=zero flow.
Tube 32-bit Integer Registers
ARRAY.REGISTER DESCRIPTION
USAGE
NOTE
2.0
Log period, Seconds
Read/Write
2.1
Julian timestamp of most recent AIU download
Read/Write
1
2.2
Julian timestamp of most recent live component update (not
aiu)
Read/Write 1
2.3
Julian timestamp of prev day period
Read Only
1
2.4
Total Slip Seconds
Read Only
2.5
Last Slip Seconds Time
Read Only
Note: Julian time is number of seconds since midnight, 1/1/1970.
Tube Floating Point Registers
ARRAY.REGISTER DESCRIPTION FORMAT
USAGE
NOTE
3.0
Current AP / cal checks
PSI
Read/Write
1
3.1
AP High Limit
PSI
Read/Write
1
3.2
AP Low Limit
PSI
Read/Write
1
3.3
Current Temp
Deg F
3.4
Fixed Temp
Deg F
3.5
Temp High Limit
Deg F
3.6
Temp Low Limit
Deg F
3.7 Flow
Rate
High
Limit
Read/Write
2
3.8
Flow Rate Low Limit
Read/Write
2
3.9
DP/ACF Percent High for Day
Read Only
3.10
DP/ACF Percent Low for Day
Read Only
3.11
Fixed F(b) AGA-3 1985
Read/Write
3.12
Fixed Cd AGA-3 1992
Read/Write
3.13 Zba
Read/Write
3.14
Orifice coef of expansion
In/Deg F
Read/Write
3.15
Pipe coef of expansion
In/Deg F
Read/Write
3.16 Barometric
Pressure PSIA
Read/Write
3.17
F(t) for Fpv NX19
Read/Write
3.18
F(p) for Fpv NX19
Read/Write
3.19 Fixed
Analysis
BTU
BTU/SCF
Read/Write
3.20 Fixed
Analysis
Gravity
Read/Write
3.21
Fixed Analysis Nitrogen
Mole %
Read/Write
3.22
Fixed Analysis Carbon Dioxide
Mole %
Read/Write
3.23
Fixed Analysis Hydrogen Sulfide
Mole %
Read/Write
Summary of Contents for XRC6490
Page 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Page 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Page 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Page 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Page 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Page 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...