A-19
48 - R1 > 0 (True if Greater than zero)
49 - R1 < 0 (True if Less than zero)
6.
Array Operations are executed when the corresponding register in array 19 is read. The
registers in array 20 contain operation codes specifying the array operation to be performed. The
registers in arrays 21 and 22 contain the operands of the array operations. The result of the
operation is returned in the registers in array 19. The following operation codes are supported:
70 - Array Addition
71 - Array Linear Average
72 - Array Square Root Average
73 - Array Minimum
74 - Array Maximum
80 - Copy Array
81 - Move Array
7.
Register 255.0 contains the number of Periodic Operations. It determines the size of arrays 0
through 6 and 23.
8.
Register 255.1 contains the number of Math Operations. It determines the size of arrays 7
through 10 and 24.
9.
Register 255.2 contains the number of Bit Operations. It determines the size of arrays 11
through 14 and 25.
10.
Register 255.3 contains the number of Compare Operations. It determines the size of arrays 15
through 18 and 26.
11.
Register 255.4 contains the number of Array Operations. It determines the size of arrays 19
through 22 and 27.
12.
These registers only exist if 255.5 thru 9 , 11, 13, 15, 17, 19, 21, 23, 25 and 27 are set to a 1 ( or
yes).
13.
Select Operations are executed when the corresponding register in array 32 is read. The
registers in array 29 contain the value that is used to switch the output between two input values
. The registers in arrays 30 and 31 contain the inputs to the operation.. The result of the select
operation is returned in the corresponding register in array 32.
14.
Lag Operations are executed when the corresponding register in array 36 is read. The registers
in array 34 contain the value that is used as the lag interval . The register in array 35 contains
the input to the operation.. The result of the lag operation is returned in the corresponding
register in array 36.
15.
Lead Operations are executed when the corresponding register in array 40 is read. The registers
in array 38 contain the value that is used as the lead interval . The register in array 39 contains
the input to the operation.. The result of the lead operation is returned in the corresponding
register in array 40.
16.
Queue Operations are executed when the corresponding register in array 46 is read. The
registers in array 42 contain the value that is used as the queue interval . The register in array
45 contains the input to the operation. The register in array 43 specifies the starting register
address for the array. The register in array 44 specifies the number of registers in the array. The
result of the queue operation is returned in the corresponding register in array 46.
17.
Ramp Operations are executed when the corresponding register in array 50 is read. The
registers in array 48 contain the value that is used as the slope. The register in array 39 contains
the input to the operation.. The result of the ramp operation is returned in the corresponding
register in array 50.
Summary of Contents for XRC6490
Page 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Page 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Page 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Page 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Page 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Page 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Page 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...