STE 73995
– 78 –
TRANSPORTATION AND INSTALLATION MANUAL
Reference: The power capacity of each servo motor is calculated by the following
equation.
(Power capacity of servo driver) = Servo rated output / 0.7
c) Example of calculating power capacity
The power capacity of TH series robot is listed in the following table.
Table 5.3 Power capacity of TH series robots
Type of robot
Control unit power
capacity [VA]
Servo driver power
capacity [VA]
Controller power
capacity [VA]
TH250A
208 715 923
TH350A
208 715 923
TH180
208 356 564
TH350A
‐
T
208 715 923
Note: The above power capacity is required when all axes are continuously operated
under 100% load. If the power capacity is insufficient when the robot is
operated, troubles such as a drop in master power voltage, a malfunction, or
resetting of the control power may take place. Thus, the robot may not be
correctly operated.
Also, an electric current that is three (3) times the rated current may be
required at the start of the robot. Thus, it is necessary to select a power
supply in which the peak current of the power is three (3) times the rated
current for 100 ms.