-2. Troubleshooting
8
-2-1. Outline of judgment
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with
the following method.
Method to judge the erroneous position by flashing indication on the display part of the indoor unit (sensors of
the receiving part)
The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis
are displayed restricted to the following cases if a protective circuit works.
: Go off,
: Go on,
: Flash (0.5 sec.)
Lamp indication
Check code
Cause of trouble occurrence
Operation
Timer
Ready
No indication at all
—
Power supply OFF, miswiring between receiving unit and indoor unit,
miswiring of power supply of outdoor unit, or power supply error.
Operation
Timer
Ready
Flash
E01
Receiving error
Receiving unit
Sending error
Communication stop
Miswiring or wire connection error
between receiving unit and indoor unit
E02
E03
E08
Duplicated indoor unit No.
Duplicated header units of remote
controller
Setup error
E09
E10
Communication error between CPUs on indoor unit P.C. board
E18
Wire connection error between indoor units, Indoor power OFF
(Communication stop between indoor master and follower or between main
and sub indoor twin)
Operation
Timer
Ready
Flash
E04
Miswiring between indoor unit and outdoor unit or connection error
(Communication stop between indoor and outdoor units)
Operation
Timer
Ready
Alternate flash
P01
Overflow was detected.
Indoor DC fan error
Protective device of indoor unit worked.
P10
P12
Operation
Timer
Ready
Alternate flash
P03
Outdoor unit discharge temp. error
High pressure SW system error
Protective device of outdoor unit
worked.
P04
P05
Open phase detection error, Power supply voltage error
Heat sink overheat error
Gas leak detection error
Outdoor unit error
P07
P15
P20
Outdoor unit high pressure protection
P22
Outdoor unit : Outdoor unit fan error
Outdoor unit : Inverter Idc operation
Outdoor unit : Position detection error
Protective device of outdoor
unit worked.
P26
P29
P31
Stopped because of error of other indoor unit in a group
(Check codes of E03/L03/L07/L08)