Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[P22]
[Fan system error]
Is AC mains voltage correct?
(AC342 to 457V)
Is the power device on P.C.board
screwed without looseness?
(IC300 of MCC-1626)
Are radiation grease properly applied?
(IC300 of MCC-1626)
Does something block the
ventilation around the heat sink?
Does something block air flow
from the fan ?
Rotate shaft of the fan motor by hands
during power-OFF. Can it rotate smoothly?
Is coil resistance of fan motor correct?
Between red and white lead wire
: 12 to 20
Ω
Between white and black lead wire : 12 to 20
Ω
Between black and red lead wire
: 12 to 20
Ω
NO
YES
NO
NO
YES
YES
YES
YES
Check outdoor P.C.Board.
Defect
→
Replace
Check wiring construction.
Ask repair of power supply.
Apply radiation grease to
objective parts.
Retightening of screws.
Remove blocking matter.
Correct short-circuit.
Replace fan motor
- 57 -
FILE NO. SVM-17005