Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[P05]
[Power supply error]
Confirm electric construction, etc.
Check outdoor P.C. board.
Defect
→
Replace
YES
NO
NO
Is there no down or up
of power supply voltage?
(AC342 to 457V)
Correct wiring
YES
Is there no open phase
of the power supply?
[P07]
[Heat sink overheat error]
Check outdoor P.C. board.
Defect
→
Replace
Remove blocking matter.
Correct short-circuit.
Does something block the
ventilation around the heat sink?
Does something block air flow
from the fan?
Apply radiation grease to objective parts.
Retightening of screws.
NO
NO
YES
YES
Is the power device on P.C. board
screwed without looseness?
(Q200 of MCC-1627)
Are radiation grease properly applied?
(Q200 of MCC-1627)
[P15]
[Gas leak detection]
Check outdoor P.C. board.
Defect
→
Replace
Repair defective position.
Replace defective part.
Repair defective position.
Recharge refrigerant.
Is PMV under correct conditions?
Is there gas leak?
Is there refrigerant shortage?
NO
YES
YES
NO
Open service valve fully.
Correct and replace piping.
Correct connector.
Sensor error
→
Replace
Is there crushed pipe?
Is service valve fully opened?
Check temp. sensor.
TD sensor CN603
TS sensor CN600
Error
OK
YES
YES
NO
NO
- 55 -
FILE NO. SVM-17005