3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by current transformer
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
I
1
I
1 – 0.5
Current [A]
Frequency down
Normal operation
Hold
Hold
Model
SM110
SM140
COOL HEAT COOL HEAT
I1 value [A]
12.5
12.5
12.5
12.5
4. Outdoor fan control
Allocations of fan tap revolutions [rpm]
Model
W1
W2
W3
W4
W5
W6
W7
W8
W9
WA
WB
WC
WD
WE
WF
SM110
2
50
2
80
330
3
60
410
460
5
20
580
640
700
760
860
900
930
930
SM140
2
50
2
80
330
3
60
410
460
5
20
580
640
700
760
860
900
930
930
4-1. Cooling fan control
1) An outdoor fan is controlled by TL sensor, TO sensor and compressor frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TL sensor temperature after then.
+
1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
Rotational frequency hold
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
SM110, 140 : WD tap
TL
55˚C
38˚C
35˚C
58˚C
Temp.
range
SM110
SM140
34.2 Hz or lower 34.2Hz to 52.2Hz 52.2Hz or higher
Min.
Max.
Min.
Max.
Min.
Max.
38°C
≤
TO
W6
WD
W8
WD
WA
WD
29°C
≤
TO < 38°C
W5
WC
W7
WC
W9
WD
15°C
≤
TO < 29°C
W3
W7
W5
W9
W7
WB
5°C
≤
TO < 15°C
W2
W5
W4
W7
W6
W9
0°C
≤
TO < 5°C
W1
W3
W3
W5
W4
W7
–4°C
≤
TO < 0°C
W1
W2
W2
W4
W3
W5
TO < –4°C
OFF
W2
OFF
W4
OFF
W4
TO error
OFF
WD
OFF
WD
OFF
WD
- 37 -
FILE NO. SVM-17005