Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[P20]
[High pressure protective operation]
Reset the power supply
and then make a test run.
Open service valve fully.
Check outdoor fan.
Defect
→
Replace, retightening
Is service valve
fully opened?
Is there any defect such as
loosening of nut in the outdoor fan?
Does the outdoor fan perform
abnormal operation?
Is resistance value
of TE sensor correct?
Replace TE sensor.
Check the same items as
[P22] error.
Check overcharge of refrigerant, clogging of cycle,
broken pipe, abnormal overload, etc.
Defect
→
Correct defect.
Eliminate interfering element.
Is there anything
which interfere heat exchange
of outdoor unit?
• Clogging of heat exchanger
• Short-circuit
YES
YES
NO
NO
YES
NO
NO
YES
YES
NO
- 56 -
FILE NO. SVM-17005