Temperature sensor
Temperature – Resistance value characteristic table
TE, TS, TO sensors
Representative value
Temperature
(°C)
Resistance value (k
Ω
)
(Minimum value) (Standard value) (Maximum value)
0
32.33
33.80
35.30
10
19.63
20.35
21.09
20
12.23
12.59
12.95
25
9.75
10.00
10.25
30
7.764
7.990
8.218
40
5.013
5.192
5.375
50
3.312
3.451
3.594
60
2.236
2.343
2.454
70
1.540
1.623
1.709
80
1.082
1.146
1.213
90
0.7740
0.8237
0.8761
100
0.5634
0.6023
0.6434
TD
, TL
sensors
Representative value
Temperature
(°C)
Resistance value (k
Ω
)
(Minimum value) (Standard value) (Maximum value)
0
150.5
161.3
172.7
10
92.76
99.05
105.6
20
58.61
62.36
66.26
25
47.01
49.93
52.97
30
37.93
40.22
42.59
40
25.12
26.55
28.03
50
17.00
17.92
18.86
60
11.74
12.34
12.95
70
8.269
8.668
9.074
80
5.925
6.195
6.470
90
4.321
4.507
4.696
100
3.205
3.336
3.468
Resistance (k
Ω
) (50ºC or lo
w
er)
Resistance (k
Ω
) (50ºC or higher)
0
0
50
100
150
200
0
5
10
15
20
10
20
30
40
50
60
70
80
90 100
Temperature (ºC)
Resistance (k
Ω
)
0
0
10
20
30
40
Output v
oltage (V)
10
20
30
40
50
60
70
80
90 100
Temperature (ºC)
TE, TS, TO sensors
TD
, TL
sensors
∗
As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the
resistance value cannot be measured.
- 59 -
FILE NO. SVM-17005