Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[H03]
[Current detection circuit error]
Check outdoor P.C. board.
Defect
→
Replace
[H04]
[Case thermostat operation]
Check crushed or broken pipe.
Defect
→
Correct and Replace
Correct defective position.
Replace defective part.
Open service valve fully.
Repair defectives position.
Recharge refrigerant.
Check outdoor P.C. board.
Defect
→
Replace
Correct connector.
Case thermostat error
→
Replace
Is service valve fully opened?
Is PMV under correct conditions?
Is there gas leak?
Is there refrigerant shortage?
Are CN500 connection and
case thermostat correct?
Short each pins of CN500.
Can compressor operate?
YES
YES
NO
YES
YES
NO
NO
YES
NO
NO
[L10]
[Unset model type]
: Only when service P.C. board is used
Cut jumper line according
to the explanation sheet packaged
with the service P.C. board.
[L29]
[Communication error between MCUs]
Check outdoor P.C. board.
Defect
→
Replace
[P03]
[Discharge temp. error]
Check outdoor P.C. board.
Defect
→
Replace
Correct connector.
Sensor error
→
Replace
Remove and improve
the cause of overload.
Repair defective position.
Replace defective part.
Repair defective position.
Recharge refrigerant.
Does an abnormal overload happen?
Is PMV under correct conditions?
Is connection of CN603 correct?
Is resistance value of TD sensor correct?
Is there gas leak?
Is there refrigerant shortage?
NO
YES
NO
YES
YES
NO
NO
YES
- 53 -
FILE NO. SVM-17005