5. PARTS RATING
5-1. Parts Rating
5-1-1.
2-Way Air Discharge Cassette Type
Model name
Fan motor
Drain pump motor
Float switc
TA sensor
TC1 sensor
TC2 sensor
TCJ sensor
Pulse motor
PMV
MMU-
AP0072WH AP0092WH AP0122WH AP0152WH AP0182WH AP0242WH AP0272WH AP0302WH
SWF-230-60-1R
SWF-280-60-1R
ADP-1409
FS-0218-103
Lead wire length 268 mm
Ø4 size lead wire length : 1200 mm, vinyl tube (Blue)
Ø6 size lead wire length : 1200 mm vinyl tube (Black)
Ø6 size lead wire length : 1200 mm vinyl tube (Red)
EMD-MD12TF-3
EFM-25YGTF-1
EFM-40YGTF-2
Model name
Fan motor
Drain pump motor
Float switc
TA sensor
TC1 sensor
TC2 sensor
TCJ sensor
Pulse motor
PMV
MMU-
AP0362WH
AP0482WH
AP0562WH
SWF-280-120-2R
ADP-1409
FS-0218-103
Lead wire length : 268 mm
Ø4 size lead wire length : 1200 mm vinyl tube (Blue)
Ø6 size lead wire length : 1200 mm vinyl tube (Black)
Ø6 size lead wire length : 1200 mm vinyl tube (Red)
EMD-MD12TF-3
EFM-60YGTF-1
5-1-2. Indoor Unit (Other Parts)
No.
1
2
Part name
Fan motor
(Model: SWF-230-60-1R)
Fan Motor
(Model: SWF-280-120-2R)
Checking procedure
Measure the resistance value of winding by using the tester.
Position
Red - White
White - Black
Black – Red
Resistance value
87 ± 8.7
Ω
Under 20°C
Measure the resistance value of winding by using the tester.
Position
Red - White
White - Black
Black – Red
Resistance value
37 ± 3.7
Ω
Under 20°C