129
Screw
Screw
Screw
Screw
Hanging construction
Hanging construction
In case of AP027/AP048
Slacken wire.
Slacken wire.
Fan motor wires
Fan motor wires
Control P.C. board
Control P.C. board
Card edge spacer
Card edge spacer
Electric parts box
Screw
Screw
Hanging construction
Slacken wire.
Fan motor wires
Control P.C. board
Card edge spacer
1
No.
3
Part name
Electric parts box
(Continued)
Procedure
6) Take off screws in the electric parts box.
(Ø4 × 8, 2 pcs.)
7) The hanging structure is set at the side
of the electric parts box. Remove the
electric parts box by sliding it to the
arrow mark in the figure.
2. Attachment
1) Attach the electric parts box and then
connect with wires as original.
2) Be sure to perform wiring in the electric
parts box as original.
Note)
For the connectors, check there is no coming-
off or connection error.
In cases of AP027 and AP048, slacken the fan
motor wires at side of the electric parts box.
(As the air filter will be entered, slackness is
required.)
3) Attach both air filter and center panel as
original.
Remarks
1. Detachment
1) Perform work Detachment 1 of
3
.
(In the works of 1 of
3
, detachment of
the control P.C. board is possible even if
skipping works 6) and after.)
2) Unlock the locks of the card edge
spacers (at 6 positions) in the electric
parts box and then remove the control
P.C. board.
2. Attachment
1) Attach the control P.C. board in the
electric parts box as original.
2) Attach the electric parts box as original.
3) Be sure to perform wiring in the electric
parts box as original.
Note)
For the connectors, check there is no coming-
off or connection error.
In cases of AP027 and AP048, slacken the fan
motor wires at side of the electric parts box.
(As the air filter will be entered, slackness is
required.)
4) Attach both air filter and center panel as
original.
4
Control P.C. board