SMMS 2-way Air Discharge Cassette Type
Installation Manual
23
EN-45
EN-46
W
ith a remote controller-less system (group control)
Besides the switching method using the wired remote controller as a way to establish the high-ceiling and filter
settings, switching is also possible by changing over the short plug settings on the indoor printed circuit board as
shown in the following table.
* However, once these settings are changed, 0001 can be set easily, but bear in mind that to return to the 0000 data,
it will be necessary to change the short plugs over to the standard (factory setting) positions and rewrite the data
back to SET DATA 0000 from the wired remote controller.
• Change over the short plugs on the indoor printed circuit board, and select the desired setting.
SET DATA
0000
0001
0003
Ceiling height
2.7 m
3.2 m
(AP007 to AP030)
3.8 m
(AP007 to AP030)
3.0 m
(AP036 to AP056)
3.5 m
(AP036 to AP056)
Filter
Standard filter
(Factory setting)
Super long life filter
—
Short plug positions (CN112, CN111 and CN110 from the left)
Short
Open
Short plug
position
Change of lighting time of filter
sign
According to the installation condition, the lighting time of
the filter sign (Notification of filter cleaning) can be
changed.
Follow the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [01].
• For the SET DATA in Procedure
4
, select the SET
DATA of Filter sign lighting time from the following
table.
T
o secure better effect of heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [06].
• For the SET DATA in Procedure
4
, select the SET
DATA of Detection temp shift value to be set up from
the following table.
Group control
In a group control, a remote controller can control up to
maximum 8 units.
• For wiring procedure and wiring method of the
individual line (Identical refrigerant line) system, refer
to “ELECTRICAL WORK” in this Manual.
• Wiring between indoor units in a group is performed in
the following procedure.
Connect the indoor units by connecting the remote
controller inter-unit wires from the remote controller
terminal blocks (A/B) of the indoor unit connected with
a remote controller to the remote controller terminal
blocks (A/B) of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
V
entilator (procured locally)
Select this setting when a locally procured ventilator has
been connected.
Follow the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [31].
• Select “0001” as the SET DATA in procedure
4
.
SET DATA
Filter sign lighting time
0000
None
0001
150 hours
0002
2500 hours (Factory setting)
0003
5000 hours
0004
10000 hours
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C (Factory setting)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
SET DATA
Ventilator
0000
Not provided (Factory setting)
0001
Provided