136
No.
10
Part name
Drain pump
Procedure
1. Detachment
1) Perform work Detachment 1 of
9
.
2) Pick the hose band and shift it from the
pump connecting part and then remove the
drain hose.
3) Take off screws which fix the drain pump
assembly and then remove the drain pump
assembly. (Ø4 × 8, 3 pcs.)
2. Attachment
1) Using screws taken off from the drain pump
assembly, fix the assembly as original.
2) Fix the drain pump wiring to the slit for
fixing the drain pump/sensor wiring.
3) Connect the drain pump as original and
then attach the hose band.
Note)
Insert the drain hose up to the back of the pup
connecting part, and apply a band at the white
mark of the hose.
4) Attach all the drain pan, partition board,
electric parts box ceiling panel, air filter and
center panel as original.
For wiring in the electric parts box, be sure
to wire it as original.
Remarks
PMV motor
PMV main unit
Relay connector: AP048 type only
Relay connector: AP048 type only
(Inside of vinyl tube (Black))
(Inside of vinyl tube (Black))
Relay connector: AP048 type only
(Inside of vinyl tube (Black))
1. Detachment
1) Perform work Detachment 1 of
8
.
2) Remove the relay connector of PMV motor.
(Only relay connector of AP048 type is
connected in the vinyl tube. Therefore cut
off the bundling band which fixes the tube
and then remove the relay connector.)
3) Peel off the butyl rubber adhered to PMV
main unit until you can see PMV main unit,
loosen nut which fixes PMV motor with
double spanner and then remove PMV
motor.
2. Attachment
1) Attach PMV motor and relay connector as
original.
Note)
Control the tightening torque of PMV main unit
and PMV motor at 7.84 ± 0.98 Nm.
PMV motor
11
Shift to hose side.
Shift to hose side.
Total 3 screws
Drain pump assembly
Drain pump assembly
Hose band
Hose band
Slit for fixing drain
Slit for fixing drain
pump/sensor wiring
pump/sensor wiring
Drain pump/sensor wiring
Shift to hose side.
Drain pump assembly
Hose band
Slit for fixing drain
pump/sensor wiring