134
No.
9
Part name
Drain pan
Procedure
1. Detachment (In case of AP009)
1) Perform work Detachment 1 of
3
.
Perform work Detachment 1 of
7
.
2) Take off the drain cap and then extract
accumulated drain water in the drain pan.
Note)
When taking off the drain cap, be sure to receive
drain water in a bucket, etc.
3) Remove the bell mouth followed to work of
Detachment 1 of
5
and release fixing of the
fan motor.
4) Remove the fan motor wiring from clamp on
the partition board.
5) Take off screw (Ø4 × 8, 1 pc.) which fixes the
partition board and then remove it as if lifting
up it.
6) Take off screws at 4 corners (Ø4 × 8, 4 pcs.)
which fix the drain pan and then pull out the
drain pan quietly.
2. Attachment (In case of AP009)
1) Attach the drain pan as original while passing
the fan motor wiring and the drain pump/
sensor wiring through the specified hole.
Note)
Be sure to pass the drain pump sensor wiring
through the specified fixing slit of the inner foaming.
Be sure to pass also the fan motor wiring through the
clamp and the fixing slit.
2) Attach all the partition board, bell mouth,
electric parts box, ceiling panel, air filter and
center panel as original.
For wiring in the electric parts box, be sure to
wire it as original.
Remarks
Drain pump/sensor wiring fixing slit
Drain pump/
Drain pump/
sensor wiring
sensor wiring
Inner foaming
Inner foaming
In case of AP009
Drain pan
Fan motor
Fan motor
wire
wire
Bell mouth
Drain cap
Fan motor wiring
Fan motor wiring
fixing slit
fixing slit
Fan motor wire
Fan motor wire
Clamp
Clamp
Screw
Screw
Partition board
Partition board
Total 4 screws
Total 4 screws
Screws
Screws
Drain pump/
sensor wiring
Inner foaming
Fan motor
wire
Fan motor wiring
fixing slit
Fan motor wire
Clamp
Screw
Partition board
Total 4 screws
Screws