Autoped Installation Manual rev 2.0 (100722)
52
XII.4 CHART FOR MENUS AND WHAT THEY DO
Menu Title
Description
PARAMETER
Sets the parameters for swing Door/Gate movements
CONFIG
Configuration: sets the configuration of the AutoPed control features and functions
DOUBLE DOOR
Sets the closing sequence and interlock function for double door applications
DIAGNOSTICS
Diagnostic tools that display the status of various inputs
ERROR ACTIVE
❖
Displays pending active errors
❖
A0 indicates the latest active error
HISTORY ERROR
❖
Displays all active errors that were detected and then corrected or not corrected.
❖
H0 indicates the latest active error
REINT
Reinitialization resets settings back to factory default
BLOCK?
Locks/unlocks joystick
UPDATE SW
Start the software upgrade process from a USB stick
TEACH
❖
Programs the initial setup, finds errors (if any)
❖
Programs a new setup procedure when necessary
XII.5 PARAMETER MENU: SETTINGS FOR DOOR/GATE MOVEMENT
Device
Unit type
Default
Value
Description
Region
Low Energy
US
US
US- united states
Software version decided by UL standards
Vo
Low energy
9
0-9
Velocity of opening 9=fastest, 0=slowest
Vc
Low energy
9
0-9
Velocity of closing 9= fastest, 0= slowest
TOEx
Low energy
5s
3-60s
Sets the hold open time for the OEO or OEI input commands. ANSI
156.19 for low energy: TOEx must be no less than 5 seconds.
TKey
Low energy
5s
3-180s
❖
TKey sets the hold open time resulting from an activation signal
from a device (referred to as KEY) on terminal X102
❖
With TOEx and TKey, you can set a different hold open time for
different activation devices by using different terminals
TPuGo Low energy
3s
3-180s
Determines how long the Door/Gate stays open when activated by the
push and go feature.
TDelay Low energy
.2s
0.0-4.0s
Tdelay sets the amount of time the door hesitates to allow the lock to
release before opening.
FDelay Low energy
Off
Off-7.0A
Fdelay is a temporary “hold closed” force applied to the door to keep it
closed while the electric lock is released. This parameter sets the
amount of force applied. FDelay is only active if TDelay setting is
greater than 0.
Summary of Contents for AUTOPED M10S.0028
Page 1: ...Autoped Installation Manual rev 2 0 100722 1 AUTOPEDTM OPERATOR INSTALLATION MANUAL 2022...
Page 40: ...Autoped Installation Manual rev 2 0 100722 40 SECTION X SETTING UP ELECTRIC LOCKS AND STRIKES...
Page 50: ...Autoped Installation Manual rev 2 0 100722 50 SECTION XII MENUS AND PROGRAMMING...
Page 59: ...Autoped Installation Manual rev 2 0 100722 59 SECTION XIII TROUBLE SHOOTING AND ERROR CHARTS...
Page 69: ...Autoped Installation Manual rev 2 0 100722 69 Fig XIV 2b Non Powered Activation Devices...
Page 75: ...Autoped Installation Manual rev 2 0 100722 75 Fig XIV 2f Secured Activation Devices...
Page 76: ...Autoped Installation Manual rev 2 0 100722 76 Fig XIV 2g Wiring for Double Door Gate System...
Page 77: ...Autoped Installation Manual rev 2 0 100722 77 SECTION XV SERVICE PARTS...
Page 78: ...Autoped Installation Manual rev 2 0 100722 78 XV 1 SERVICE PARTS COMPONENTS VISUAL GUIDE...
Page 80: ...Autoped Installation Manual rev 2 0 100722 80 SECTION XVI PRODUCT WARRANTY AND REGISTRATION...