212
212
NC20 - Manual - 01 - 2015
APPENDIX
212
212
NC20 - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN> Logical block
IN>BLK1
OFF | ON
IN> Input selective block
IN>BLK2IN
OFF | ON
IN> Output selective block
IN>BLK2OUT
OFF | ON
IN> Breaker failure
IN>BF
OFF | ON
IN>AL Disabling by IN>
IN>ALdisbyIN>
OFF | ON
IN> Start relays
IN>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IN> Trip relays
IN>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IN> Start LEDs
IN>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
IN> Trip LEDs
IN>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
46N First threshold defi nite time
State
OFF | ON
Pickup value
INn
0.01 ... 2.00 step = 0.01
IN>def within CLP
INCLP>def
INn
0.01 ... 2.00 step = 0.01
IN>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 50.0 step = 0.1
Inverse time
46N First threshold inverse time
State
OFF | ON
Pickup value
INn
0.01 ... 1.00 step = 0.01
IN>inv within CLP
INCLP>inv
INn
0.01 ... 1.00 step = 0.01
IN>inv Operating time
tN>inv
s
0.02 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
IN>> Element
Setpoints
IN>> Enable
IN>> Enable
OFF | ON
INCLP>> Mode
INCLP>> Mode
OFF | ON - Element blocking | ON - Change setting
INCLP>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN>> Logical block
IN>>BLK1
OFF | ON
IN>> Input selective block
IN>>BLK2IN
OFF | ON
IN>> Output selective block
IN>>BLK2OUT
OFF | ON
IN>> Breaker failure
IN>>BF
OFF | ON
IN>AL Disabling by IN>>
IN>ALdisbyIN>>
OFF | ON
IN> Disabling by IN>>
IN>disbyIN>>
OFF | ON
IN>> Start relays
IN>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IN>> Trip relays
IN>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IN>> Start LEDs
IN>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
IN>> Trip LEDs
IN>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
46N Second threshold defi nite time
State
OFF | ON
Pickup value
INn
0.01 ... 2.00 step = 0.01
IN>>def within CLP
INCLP>>def
INn
0.01 ... 2.00 step = 0.01
IN>>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 50.0 step = 0.1
Thermal image - 49