Description
Parameter Unit
Setting range
U>> Start LEDs
U>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
U>> Trip LEDs
U>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
59 Second threshold defi nite time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
U>>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Trip circuit supervision - 74TCS
74TCS Enable
74TCS Enable
OFF | ON
74TCS Logical block
74TCS-BLK1
OFF | ON
74TCS Start relays
74TCS-ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
74TCS Trip relays
74TCS-TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
74TCS Start LEDs
74TCS-ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
74TCS Trip LEDs
74TCS-TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Selective block - BLOCK2
Selective block IN
BLIN1 Selective block operating mode
ModeBLIN1
OFF | ON IPh/IE | ON IPh | ON IE
BLIN maximum activation time for phase protections
Value
s
0.10 ... 10.00 step = 0.01
BLIN maximum activation time for ground protections
Value
s
0.10 ... 10.00 step = 0.01
tB-Iph/IE Elapsed signalling relays
tB-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
tB-Iph/IE Elapsed signalling LEDs
tB-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Selective block OUT
BLOUT1 Selective block operating mode
ModeBLOUT1
OFF | ON IPh/IE | ON IPh | ON IE
BLOUT Dropout time for phase protections
Value
s
0.00 ... 1.00 step = 0.01
BLOUT Dropout time for ground protections
Value
s
0.00 ... 1.00 step = 0.01
BLOUT Dropout time for ground and phase protections
Value
s
0.00 ... 1.00 step = 0.01
Phase protections output selective block relays
BLK2OUT-Iph-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Ground protections output selective block relays
BLK2OUT-IE-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Phase and ground protections output selective block
relays
BLK2OUT-Iph/
IE-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Phase protections output selective block LEDs
BLK2OUT-Iph-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Ground protections output selective block LEDs
BLK2OUT-IE-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Phase and ground protections output selective block
LEDs
BLK2OUT-Iph/
IE-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Breaker failure - BF
BF Enable
BF Enable
OFF | ON
BF Phase current threshold
State
OFF | ON
Pickup value
In
0.05 ... 1.00 step = 0.01
BF Residual current threshold
State
OFF | ON
Pickup value
In
0.05 ... 1.00 step = 0.01
BF Time delay